中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLMZ4D-SKX1
LMZ4D-SKX1 State Grid Standard 0.66kV Current Transformer
0.66kVLMZ4D-SKX1
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 0.66kV
Secondary Metering (1S1 - 1S2):5A (0.2S/0.5S)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LMZ4D-SKX1

LMZ4D-SKX1 State Grid Standard 0.66kV Current Transformer

Indoor epoxy cast LV current transformer, State Grid standard, primary rated current 800-1500A, accuracy 0.2S/0.5S.

Key Engineering Advantages

  • 800-1500A primary current
  • State Grid standard
  • 0.66kV
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LMZ4D-SKX1

Electrical Parameters

Primary Rated Voltage (Un):0.66kV
Secondary Winding Currents:5A
Metering & Protection Class:0.2S/0.5S
Rated Output Burden:10VA
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

LMZ4D-SKX1 is a 0.66kV indoor current transformer with 800-1500A primary, 5A secondary, accuracy 0.2S/0.5S, ideal for low-voltage metering and protection. It is not suitable for outdoor or high-voltage applications.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLMZ4D-SKX1Factory nameplate marking
Primary Voltage0.66kVRated voltage test (IEC 61869-1/3)
Secondary Current5ARatio check at rated frequency
Accuracy Class0.2S/0.5SAccuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden10VABurden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Low-voltage (0.66kV) indoor metering and protection circuits
  • State Grid standard compliant installations
  • Current measurement with high accuracy (0.2S/0.5S)
  • 50/60Hz power systems
  • Dry environment with epoxy resin insulation

Not Recommended For

  • Outdoor installations without additional protection
  • High-voltage systems above 0.66kV
  • DC applications
  • High burden requirements exceeding 10VA
  • Environments with high humidity or corrosive gases

Topology & Wiring

Connect primary terminals P1/P2 in series with the line. Secondary terminals are 1S1/1S2 for the main winding; if dual ratio, use 2S1/2S2 for the second winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Ensure the secondary burden does not exceed 10VA. Follow IEC 61869-2 and IEEE C57.13 conventions.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the primary current range of LMZ4D-SKX1?

A: The primary current range is 800-1500A.

Q: What accuracy class does this CT offer?

A: It offers 0.2S/0.5S accuracy class.

Q: Can this CT be used outdoors?

A: No, it is designed for indoor use only.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LMZ4D-SKX1
5 cols · 5 rows

LMZ1 (2,3,4)D Series Current Transformer — Technical Data

ModelRated primary current (A)Rated output (VA) 0.2 classRated output (VA) 0.5 classPrimary turns
LMZ1D-SKX175551
LMZ2D-SKX2100-150551
LMZ3D-SKX1200-600551
LMZ4D-SKX1600-8005101
LMZ4D-SKX1800-15005101
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LMZ4D-SKX1 — click image to zoom / view original.

Product Overview

About This Product

LMZ4D-SKX1

This current transformer is a 0.66kV indoor unit designed to step primary current down to a 5A secondary for metering and control in distribution systems, and it is built to the State Grid standard framework alongside IEC 61869, GB/T 20840 and IEEE C57.13 practice. The dry epoxy resin insulation and single-turn primary winding are supported by routine factory checks covering ratio and polarity verification and dielectric screening before dispatch.

Accuracy classes 0.2S/0.5S are offered with a rated output of 10VA at class 0.5 and 5VA at class 0.2, so the secondary burden should be matched to the declared VA window rather than exceeded. Primary current spans 600-1500A at 50/60Hz. As an indoor device it suits medium-voltage switchgear, ring main units and central withdrawable cubicles, not outdoor exposure; the 0.66kV level is a hard ceiling and step-up use is not permitted.

Primary connections follow the P1/P2 and secondary H1/H2 terminal markings, with the secondary earthed at one point; the secondary must never be open-circuited while energized. Datasheets, outline drawings and routine test reports are available [On Request], and export packing plus after-sales support are arranged at quotation.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs