Indoor epoxy cast LV current transformer, State Grid standard, primary rated current 800-1500A, accuracy 0.2S/0.5S.
LMZ4D-SKX1 is a 0.66kV indoor current transformer with 800-1500A primary, 5A secondary, accuracy 0.2S/0.5S, ideal for low-voltage metering and protection. It is not suitable for outdoor or high-voltage applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZ4D-SKX1 | Factory nameplate marking |
| Primary Voltage | 0.66kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A | Ratio check at rated frequency |
| Accuracy Class | 0.2S/0.5S | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 10VA | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary terminals P1/P2 in series with the line. Secondary terminals are 1S1/1S2 for the main winding; if dual ratio, use 2S1/2S2 for the second winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Ensure the secondary burden does not exceed 10VA. Follow IEC 61869-2 and IEEE C57.13 conventions.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary current range of LMZ4D-SKX1?
A: The primary current range is 800-1500A.
Q: What accuracy class does this CT offer?
A: It offers 0.2S/0.5S accuracy class.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated primary current (A) | Rated output (VA) 0.2 class | Rated output (VA) 0.5 class | Primary turns |
|---|---|---|---|---|
| LMZ1D-SKX1 | 75 | 5 | 5 | 1 |
| LMZ2D-SKX2 | 100-150 | 5 | 5 | 1 |
| LMZ3D-SKX1 | 200-600 | 5 | 5 | 1 |
| LMZ4D-SKX1 | 600-800 | 5 | 10 | 1 |
| LMZ4D-SKX1 | 800-1500 | 5 | 10 | 1 |
Dimension & outline drawing of LMZ4D-SKX1 — click image to zoom / view original.
This current transformer is a 0.66kV indoor unit designed to step primary current down to a 5A secondary for metering and control in distribution systems, and it is built to the State Grid standard framework alongside IEC 61869, GB/T 20840 and IEEE C57.13 practice. The dry epoxy resin insulation and single-turn primary winding are supported by routine factory checks covering ratio and polarity verification and dielectric screening before dispatch.
Accuracy classes 0.2S/0.5S are offered with a rated output of 10VA at class 0.5 and 5VA at class 0.2, so the secondary burden should be matched to the declared VA window rather than exceeded. Primary current spans 600-1500A at 50/60Hz. As an indoor device it suits medium-voltage switchgear, ring main units and central withdrawable cubicles, not outdoor exposure; the 0.66kV level is a hard ceiling and step-up use is not permitted.
Primary connections follow the P1/P2 and secondary H1/H2 terminal markings, with the secondary earthed at one point; the secondary must never be open-circuited while energized. Datasheets, outline drawings and routine test reports are available [On Request], and export packing plus after-sales support are arranged at quotation.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.