Indoor epoxy resin casting current transformer complying with GB/T20840.1, GB/T20840.2, IEC61869-1 and IEC61869-2 standards, rich primary current specifications and multi-type accuracy grades optional for different application scenarios.
Indoor epoxy resin CT for 12kV systems; suitable for measurement and protection in RMU applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | GB/T20840.1, GB/T20840.2, IEC61869-1, IEC61869-2 |
| Model Code | LMZ8-10 | Factory nameplate marking |
| Primary Voltage | 10 kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A or 1A | Ratio check at rated frequency |
| Accuracy Class | 0.2S, 0.5, 10P20, 10P10 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | GB/T20840.1, GB/T20840.2, IEC61869-1, IEC61869-2 | Certified to listed standards |
| Frequency | 50Hz or 60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
connect secondary terminals 1S1/1S2 for measurement, and 2S1/2S2 for protection if dual-winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: GB/T20840.1, GB/T20840.2, IEC61869-1, IEC61869-2
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary voltage rating?
A: The primary voltage is 12/42/75 kV, indicating a 12kV system with 42kV power-frequency and 75kV lightning impulse withstand.
Q: What secondary ratings are available?
A: Secondary current is 5A or 1A, as specified.
Q: What standards does it comply with?
A: It complies with GB/T20840.1, GB/T20840.2, IEC61869-1, and IEC61869-2.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Measuring class Current Transformer 0.2S | Measuring class Current Transformer 0.5 | Protection Current Transformer 10P20 | Protection Current Transformer 10P10 | Dual-winding Current Transformer 0.2S | Dual-winding Current Transformer 0.5 | Dual-winding Current Transformer 10P10 | Weight (kg) |
|---|---|---|---|---|---|---|---|---|
| 50/1 | — | 1.5 | — | 1.5 | — | — | — | 6 |
| 75/1 | — | 2.5 | — | 2.5 | — | — | — | 6 |
| 100/1 | 1.5 | 3.75 | 1.5 | 3.75 | — | 1.5 | 1.5 | 6 |
| 150/1 | 2.5 | 5 | 2.5 | 5 | — | 2.5 | 1.5 | 6 |
| 200/1 | 3.75 | 7.5 | 3.75 | 7.5 | 2.5 | 3.75 | 2.5 | 6 |
| 300/1 | 5 | 10 | 5 | 10 | 3.75 | 5 | 3.75 | 6 |
| 400/1 | 7.5 | 15 | 7.5 | 15 | 5 | 7.5 | 5 | 6 |
| 500/1 | 10 | 20 | 10 | 20 | 7.5 | 10 | 7.5 | 6 |
| 50/5 | — | — | — | 1.5 | — | — | — | 6 |
| 75/5 | — | 2.5 | — | 2.5 | — | — | — | 6 |
| 100/5 | — | 3.75 | 1.5 | 3.75 | — | — | 1.5 | 6 |
| 150/5 | 2.5 | 5 | 2.5 | 5 | — | 2.5 | 1.5 | 6 |
| 200/5 | 3.75 | 7.5 | 3.75 | 7.5 | 2.5 | 3.75 | 2.5 | 6 |
| 300/5 | 5 | 10 | 5 | 10 | 3.75 | 5 | 3.75 | 6 |
| 400/5 | 7.5 | 15 | 7.5 | 15 | 5 | 7.5 | 5 | 6 |
| 500/5 | 10 | 20 | 10 | 20 | 7.5 | 10 | 7.5 | 6 |
Dimension & outline drawing of LMZ8-10 — click image to zoom / view original.
The LMZ8-10 is a 10 kV indoor current transformer built on a dry epoxy resin insulation system, a construction that removes the liquid-handling and maintenance routines associated with oil-immersed units while keeping the secondary circuit isolated from the primary. The winding assembly is encapsulated in an integrated casting structure, and the vacuum or APG casting route is what gives the solid insulation its void-free character.
Accuracy classes span 0.2S, 0.5, 10P20 and 10P10, with rated outputs from 1.5VA to 10VA depending on the ratio; the 0.2S class holds its error band from light load through full load, which matters where tariff metering is involved. Insulation level is 12/42/75kV to GB/T20840.1, GB/T20840.2, IEC61869-1 and IEC61869-2, and calibration certificates for metering service can be supplied. Typical deployment is inside medium-voltage switchgear, ring-main units and centre-mounted cubicles.
This unit is for indoor service only and must not be installed in open-air locations. Before energising, verify the secondary burden in VA against the nameplate, earth the secondary at one point, and never open-circuit the secondary while the primary is live. Ratio and class options, documentation packages and lead times are confirmed at enquiry.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.