LMZB-20 Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 20kV, secondary voltage 5A/1A. Design: insulation level 24/65/125kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor 20kV bushing-type CT for medium-voltage switchgear, suitable for metering and protection up to 6000A.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZB-20 | Factory nameplate marking |
| Primary Voltage | 20kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 24/65/125kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary busbar through the window. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 12/42/75kV, meaning 12kV system voltage, 42kV power-frequency withstand, 75kV lightning impulse withstand.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only.
Q: What secondary currents are available?
A: Secondary current is 5A or 1A.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | 0.2(S) | 0.5(S) | 5P10 | 5P15 | 5P20 | Weight (kg) |
|---|---|---|---|---|---|---|---|
| 1500 | 0.2(S)/0.2(S)/5P 0.2(S)/0.5(S)/5P 0.2(S)/5P/5P 0.5(S)/5P/5P | 20 | 30 | 80 | 50 | 30 | 102 |
| 2000 | 0.2(S)/0.2(S)/5P 0.2(S)/0.5(S)/5P 0.2(S)/5P/5P 0.5(S)/5P/5P | 20 | 30 | 100 | 60 | 40 | 102 |
| 2500 | 0.2(S)/0.2(S)/5P 0.2(S)/0.5(S)/5P 0.2(S)/5P/5P 0.5(S)/5P/5P | 30 | 50 | 100 | 60 | 40 | 102 |
| 3000-6000 | 0.2(S)/0.2(S)/5P 0.2(S)/0.5(S)/5P 0.2(S)/5P/5P 0.5(S)/5P/5P | 30 | 50 | 100 | 80 | 50 | 102 |
Dimension & outline drawing of LMZB-20 — click image to zoom / view original.
The LMZB-20 is an indoor single-phase epoxy resin cast current transformer rated 20 kV, designed to step primary current down to 5 A or 1 A for metering and protection in 50/60 Hz systems. Its dry epoxy resin body provides the insulation, with a dielectric rating of 24/65/125 kV; details of creepage distance and winding architecture are available on the nameplate and official datasheet.
Accuracy classes include 0.2(S), 0.5(S), 5P10, 5P15 and 5P20, with rated outputs from 20 VA to 100 VA depending on the class and primary current. For example, at 1500 A the 5P10 output is 80 VA and the unit weighs 102 kg; at 2500 A the 0.2(S) output is 30 VA. The 5P cores are intended to resist saturation under fault currents, supporting reliable protection operation.
This indoor unit suits switchgear in rail, data centre, hospital and water infrastructure. Earth the secondary at one point and never open-circuit it while energized. Standard ratios are stocked; custom ratios and classes are available [On Request]. Over-specifying accuracy wastes budget. Request the datasheet, outline drawing and test reports with your inquiry.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:1000-1500A、2000-3000A、4000-6000A; accuracy combinations including 0.2S/0.2S、0.2S/0.5S、0.2S/10P15/10P15、0.5S/10P15/10P15, rated output values 15VA/20VA/30VA corresponding to different accuracy grades, net weight 45kg, ambient operating temperature -5℃~+40℃.
10kV Indoor Through-Core Epoxy Cast Current Transformer
LMZB3-10GWD,E 10kV Indoor Through-Core Epoxy Cast Current Transformer (LMZB3-10GWD-E) is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A or 1A, accuracy class 0.2S, 0.5, 5P20, 5P30. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869, GB/T 20840.
Indoor Single-phase Epoxy Resin Casting Current Transformer
Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:1000-1200A、1500A、2000-6000A; multiple accuracy combinations like 0.2S/0.5S、0.2S/10P15、10P15/10P15、0.5S/10P15, rated output values 15VA/20VA/30VA for different grades, net weight 30kg, ambient operating temperature -5℃~+40℃.