Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:1000-1500A、2000A、3000A、4000A、5000A、6000A; accuracy combinations include 0.2S/0.2S、0.2S/0.5S、0.2S/10P15、0.5S/10P15/10P15, corresponding rated output:20VA、30VA、40VA for different accuracy grades, net weight 50kg, ambient operating temperature -5℃~+40℃.
Indoor 10kV cast-resin current transformer for medium-voltage switchgear, suitable for metering and protection up to 6000A.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZB6-10G | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary busbar through the hollow window. Secondary terminals: 1S1-1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 12/42/75kV, meaning 12kV system voltage, 42kV power-frequency withstand, 75kV lightning impulse withstand.
Q: Can this CT be used for both metering and protection?
A: Yes, it offers accuracy combinations like 0.2S/10P15, with separate secondary windings for metering and protection.
Q: What is the weight of this CT?
A: The net weight is 50kg.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 0.2 (S) | Accuracy class & rated output (VA) COSφ=0.8 0.5 (S) | Accuracy class & rated output (VA) COSφ=0.8 10P15 | Weight (kg) |
|---|---|---|---|---|---|
| 1000-1500 | 0.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/10P15/10P15 0.5(S)/10P15/10P15 | 20 | 20 | 20 | 50 |
| 2000 | 0.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/10P15/10P15 0.5(S)/10P15/10P15 | 30 | 30 | 20 | 50 |
| 3000 | 0.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/10P15/10P15 0.5(S)/10P15/10P15 | 40 | 40 | 40 | 50 |
| 4000 | 0.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/10P15/10P15 0.5(S)/10P15/10P15 | 40 | 40 | 40 | 50 |
| 5000 | 0.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/10P15/10P15 0.5(S)/10P15/10P15 | 40 | 40 | 40 | 50 |
| 6000 | 0.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/10P15/10P15 0.5(S)/10P15/10P15 | 40 | 40 | 40 | 50 |
Dimension & outline drawing of LMZB6-10G — click image to zoom / view original.
The LMZB6-10G is a 10kV indoor single-phase epoxy resin cast current transformer, built to step primary current down to 5A/1A for metering and protection in medium-voltage switchgear where light-load metering error and CT saturation are the recurring concerns.
Its dry epoxy resin body with a hollow bushing and equipotential line design keeps the insulation compact, so the 50kg unit occupies little panel space in a crowded distribution room. Accuracy classes 0.2(S) / 0.5(S) / 10P15 with rated outputs of 20VA / 30VA / 40VA cover the metering range, while the 12/42/75kV insulation level suits 50/60Hz service from -5℃ to +40℃ indoors.
Selection follows the primary current: 1000-1500A and 2000A rows give 20VA or 30VA at 0.2(S), rising to 40VA from 3000A upward. Compliance follows IEC 61869, with test evidence available [On Request]. Typical deployment is indoor busbar metering and protection in substation bays. Before energizing, verify the secondary burden in VA against the rated output and earth the secondary at one point; never open-circuit the secondary while energized. This unit is not for outdoor or above-10kV service. Ratio, class and winding configurations are customized on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.