Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:400A、500A、600A、800A、1000A; accuracy combinations include 5P20/5P20/0.2S、5P20/5P20/0.5S; rated output:0.2S:15VA/20VA,0.5S:15VA/20VA,5P20:30VA, net weight 98kg, ambient operating temperature -5℃~+40℃.
LMZB8-10 is a 10kV indoor current transformer for medium voltage switchgear, suitable for metering and protection.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZB8-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through bushing. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of LMZB8-10?
A: 12kV system; power-frequency withstand 42kV; lightning impulse withstand 75kV peak.
Q: What are the available accuracy combinations?
A: 5P20/5P20/0.2S and 5P20/5P20/0.5S.
Q: What is the weight of this transformer?
A: 98kg.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSΦ=0.8 0.2 (S) | Accuracy class & rated output (VA) COSΦ=0.8 0.5 (S) | Accuracy class & rated output (VA) COSΦ=0.8 5P20 | Weight (kg) |
|---|---|---|---|---|---|
| 400 | 5P20/5P20/0.2S 5P20/5P20/0.5S | 15 | 15 | 30 | 98 |
| 500 | 5P20/5P20/0.2S 5P20/5P20/0.5S | 15 | 15 | 30 | 98 |
| 600 | 5P20/5P20/0.2S 5P20/5P20/0.5S | 15 | 15 | 30 | 98 |
| 800 | 5P20/5P20/0.2S 5P20/5P20/0.5S | 20 | 20 | 30 | 98 |
| 1000 | 5P20/5P20/0.2S 5P20/5P20/0.5S | 20 | 20 | 30 | 98 |
Dimension & outline drawing of LMZB8-10 — click image to zoom / view original.
The LMZB8-10 is an indoor single-phase epoxy resin cast current transformer for 10kV systems, designed to step primary current down to 5A or 1A for metering and protection. It is engineered within the IEC 61869, GB/T 20840 and IEEE C57.13 framework, with a 12/42/75kV insulation level and 50/60Hz rating. The dry epoxy casting and heavy-duty construction suit indoor service from -5℃ to +40℃, and the unit weighs 98kg.
Accuracy options include 0.2S or 0.5S metering classes with 15VA or 20VA output, and 5P20 protection classes rated 30VA at COSΦ=0.8. Primary current ratings span 400A to 1000A, with the 800A and 1000A rows offering 20VA metering output. This bushing-type unit sits in the indoor class, so outdoor or high-pollution service should be referred to [On Request] rather than assumed.
Typical deployment covers infrastructure such as rail, data centres, hospitals and water utilities. Before energising, perform insulation resistance, polarity and ratio checks. Never open-circuit the secondary while energised. Ratio and accuracy customisation, documentation packages and delivery terms are available on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.