Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:1000-1500A、2000A、3000A、4000A、5000A; accuracy combinations include 0.2S/0.2S、0.2S/0.5S、0.2S/5P20/5P20、0.5S/5P20/5P20, corresponding rated output values 20-60VA for different accuracy grades, net weight 45kg, ambient operating temperature -5℃~+40℃.
Indoor 10kV current transformer for switchgear panels, suitable for metering and protection up to 5000A.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZBJ9-10X | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary busbar through the window. Secondary terminals: 1S1-1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: 12kV system; power-frequency withstand 42kV; lightning impulse withstand 75kV peak.
Q: Can this CT be used for both metering and protection?
A: Yes, with dual cores (e.g., 0.2S/5P20) and separate secondary windings.
Q: What is the weight and mounting type?
A: Net weight 45kg, indoor bushing-type with epoxy resin casting.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSΦ=0.8 0.2 (S) | Accuracy class & rated output (VA) COSΦ=0.8 0.5 (S) | Accuracy class & rated output (VA) COSΦ=0.8 5P20 | Weight (kg) |
|---|---|---|---|---|---|
| 1000-1500 | — | 20 | 40 | 15 | 45 |
| 2000 | 0.2(S)/0.2(S) | 20 | 30 | 20 | 45 |
| 3000 | 0.2(S)/0.5(S) | 20 | 30 | 20 | 45 |
| 4000 | 0.2(S)/5P20/5P20 | 30 | 60 | 30 | 45 |
| 5000 | 0.5(S)/5P20/5P20 | 30 | 60 | 30 | 45 |
Dimension & outline drawing of LMZBJ9-10X — click image to zoom / view original.
The LMZBJ9-10X is a 10kV indoor single-phase epoxy resin cast current transformer, a bushing-type unit intended for current measurement and protection in medium-voltage switchgear. Its dry epoxy resin insulation and equipotential connection design suit it to panel integration where a compact, solid-insulated CT is required.
The core and windings are encapsulated in cast epoxy resin, giving a solid insulation system with an insulation level of 12/42/75kV for 50/60Hz service. Electrical performance covers accuracy classes 0.2(S), 0.5(S) and 5P20, with rated outputs of 20VA and 30VA depending on the ratio and class combination; the 5P20 protection core is intended to remain stable under fault-level primary currents. The unit weighs 45kg. Standard catalogue ratios and classes cover most specification schedules, while non-standard ratio and accuracy combinations are quoted on application; datasheets, outline drawings and routine test reports are available [On Request].
Typical deployment is in indoor distribution and heavy-industry switchgear for metallurgy, mining, cement and chemical plants. Earth the secondary at one point and observe the equipotential connection; never open-circuit the secondary while the primary is energized. The ambient range is -5℃ to +40℃, and it is not for outdoor service.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.