中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLMZC-10
LMZC-10 Indoor Foot-Fixed High-Precision Current Transformer
10kVLMZC-10
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2): (0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P))
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LMZC-10

LMZC-10 Indoor Foot-Fixed High-Precision Current Transformer

LMZC-10 Indoor Foot-Fixed High-Precision Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, accuracy class 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P), rated burden 60VA(0.2),120VA(0.5),200VA(1.0),100VA(3P). Design: Dry Epoxy Resin, 50Hz/60Hz operation.

Key Engineering Advantages

  • Foot-fixed precision CT specially designed for 10kV ring main cabinet installation
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LMZC-10

Electrical Parameters

Primary Rated Voltage (Un):10kV
Metering & Protection Class:0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P)
Rated Output Burden:60VA(0.2),120VA(0.5),200VA(1.0),100VA(3P)
Rated Frequency:50Hz/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor CT for 10kV RMU; accuracy 0.2/3P(6P) etc.; dry epoxy insulation.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLMZC-10Factory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P)Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden60VA(0.2),120VA(0.5),200VA(1.0),100VA(3P)Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50Hz/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 10kV indoor ring main units
  • Metering and protection applications
  • Indoor switchgear panels
  • Dry environment installations

Not Recommended For

  • Outdoor substations
  • Gas-insulated switchgear (GIS)
  • High-voltage transmission lines
  • DC systems

Topology & Wiring

secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal conventions.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the primary voltage rating?

A: The primary voltage is 20kV, suitable for 10kV systems.

Q: What accuracy classes are available?

A: Available accuracy classes include 0.2/3P(6P), 0.5/3P(6P), and 1.0/3P(6P).

Q: Is this CT suitable for outdoor use?

A: No, it is designed for indoor installation only.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LMZC-10
2 cols · 5 rows

LMZC-10 Series Current Transformer

ParameterValue
Product performance complies with standardsGB/T20840.1, 2 and IEC61869-1, 2
Rated insulation level0.72/3kV
Rated frequency50Hz or 60Hz
Rated secondary current5A or 1A
Ambient temperature-5℃~+40℃
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LMZC-10 — click image to zoom / view original.

Product Overview

About This Product

LMZC-10

The LMZC-10 is a 10kV indoor foot-fixed current transformer that measures primary current and supplies a proportional secondary signal to metering and protection devices in medium-voltage switchgear. Its dry epoxy resin insulation and compact foot-mounted body suit ring main cabinet installation, where the reduced footprint helps preserve cable and busbar space inside the enclosure.

The accuracy classes available are 0.2/3P(6P), 0.5/3P(6P) and 1.0/3P(6P), with rated burdens of 60VA(0.2), 120VA(0.5), 200VA(1.0) and 100VA(3P) at 50Hz or 60Hz and a rated secondary current of 5A or 1A. Compared with oil-immersed or SF6 designs, the dry resin construction removes liquid and gas handling from the indoor installation. Performance follows GB/T20840.1, 2 and IEC61869-1, 2, with a rated insulation level of 0.72/3kV.

It is intended for indoor medium-voltage switchgear and ring main cabinets, not for outdoor open-air mounting. Observe primary polarity at P1/P2 and secondary polarity at H1/H2, earth the secondary at one point, and never open-circuit the secondary while energized. The ambient range is -5℃~+40℃. Ratio and accuracy-class combinations can be customized; [On Request] for test reports and delivery schedules.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs