LMZC-10 Indoor Foot-Fixed High-Precision Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, accuracy class 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P), rated burden 60VA(0.2),120VA(0.5),200VA(1.0),100VA(3P). Design: Dry Epoxy Resin, 50Hz/60Hz operation.
Indoor CT for 10kV RMU; accuracy 0.2/3P(6P) etc.; dry epoxy insulation.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZC-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P) | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 60VA(0.2),120VA(0.5),200VA(1.0),100VA(3P) | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50Hz/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal conventions.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary voltage rating?
A: The primary voltage is 20kV, suitable for 10kV systems.
Q: What accuracy classes are available?
A: Available accuracy classes include 0.2/3P(6P), 0.5/3P(6P), and 1.0/3P(6P).
Q: Is this CT suitable for outdoor use?
A: No, it is designed for indoor installation only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Parameter | Value |
|---|---|
| Product performance complies with standards | GB/T20840.1, 2 and IEC61869-1, 2 |
| Rated insulation level | 0.72/3kV |
| Rated frequency | 50Hz or 60Hz |
| Rated secondary current | 5A or 1A |
| Ambient temperature | -5℃~+40℃ |
Dimension & outline drawing of LMZC-10 — click image to zoom / view original.
The LMZC-10 is a 10kV indoor foot-fixed current transformer that measures primary current and supplies a proportional secondary signal to metering and protection devices in medium-voltage switchgear. Its dry epoxy resin insulation and compact foot-mounted body suit ring main cabinet installation, where the reduced footprint helps preserve cable and busbar space inside the enclosure.
The accuracy classes available are 0.2/3P(6P), 0.5/3P(6P) and 1.0/3P(6P), with rated burdens of 60VA(0.2), 120VA(0.5), 200VA(1.0) and 100VA(3P) at 50Hz or 60Hz and a rated secondary current of 5A or 1A. Compared with oil-immersed or SF6 designs, the dry resin construction removes liquid and gas handling from the indoor installation. Performance follows GB/T20840.1, 2 and IEC61869-1, 2, with a rated insulation level of 0.72/3kV.
It is intended for indoor medium-voltage switchgear and ring main cabinets, not for outdoor open-air mounting. Observe primary polarity at P1/P2 and secondary polarity at H1/H2, earth the secondary at one point, and never open-circuit the secondary while energized. The ambient range is -5℃~+40℃. Ratio and accuracy-class combinations can be customized; [On Request] for test reports and delivery schedules.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.