Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges: 300-400A、500-1000A、1200-1250A、2000-6000A; multiple accuracy combinations including 0.5S/0.5S、0.2S/10P10、0.5S/10P10、0.2S/10P15、0.5S/10P15、10P15/10P15, corresponding rated output 5VA-50VA. Weight varies by current range: 10–13.5kg 300-1000A, 24kg 1200-1250A, 36kg 2000-6000A; ambient operating temperature -5℃~+40℃.
Indoor 10kV cast-resin current transformer for MV switchgear, metering, and protection.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZJ-10Q | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level?
A: 12kV system; power-frequency withstand 42kV; lightning impulse withstand 75kV peak.
Q: What secondary currents are available?
A: 5A or 1A.
Q: What accuracy classes are offered?
A: 0.5S/0.5S, 0.2S/10P10, 0.5S/10P10, 0.2S/10P15, 0.5S/10P15, 10P15/10P15.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Rated output & Rated output (VA)COSφ=0.8 (0.2 (S) / 0.5 (S) / 5P10/15 / 5P15/15) | Weight (kg) |
|---|---|---|---|
| 300-400 | 0.5(S)/0.5(S) 0.2(S)/10P10 | 5 / 10 / 15 | 10-13.5 |
| 500-1000 | 0.5(S)/10P10 0.5(S)/10P15 | 10 / 10 / 15 | 10-13.5 |
| 1200-1250 | 0.2(S)/10P15 0.5(S)/10P15 | 20 / 30 / 50 / 30 | 24 |
| 2000-6000 | 0.2(S)/10P15 0.5(S)/10P15 1S/P15/10P15 | 20 / 30 / 50 / 40 | 36 |
Dimension & outline drawing of LMZJ-10Q — click image to zoom / view original.
The LMZJ-10Q is a 10 kV indoor single-phase epoxy resin cast current transformer, engineered within the IEC 61869 series framework for metering and protection duties in medium-voltage systems. Its dry epoxy resin body provides the primary insulation, with a through-wall cast construction that integrates the primary conductor and core assembly into a single solid unit.
Electrical performance covers accuracy classes 0.2(S), 0.5(S) and 5(10)P10, with rated outputs from 5VA to 50VA depending on the primary current rating. The 12/42/75kV insulation level and 50/60Hz frequency range suit typical distribution switchgear. Weights range from 10kg to 36kg across the current range, with the 1200–1250A and 2000–6000A variants at 24kg and 36kg respectively. Standard configurations are available ex stock, while non-standard ratios and accuracy combinations are built to order.
This unit is intended for indoor installation only, within an ambient range of -5℃ to +40℃. Secondary terminals must never be open-circuited while the primary is energized, and the secondary circuit should be earthed at one point. For applications involving DC or non-standard frequencies, the transformer is not suitable. [On Request] for custom ratio and accuracy documentation packages, export packing and after-sales support details.
Same product family, different ratings — compare before you specify.
Indoor Low Voltage Current Transformer 0.5kV
Indoor low voltage current transformer, 0.5kV rated, epoxy resin casting type, for current measurement and protection in low voltage distribution systems. Complies with IEC 60044-1 and GB/T 1208 standards. Wide range of current ratios available, multiple accuracy classes 0.2, 0.5, 1.0. Compact size, easy installation, suitable for switchgear and panel mounting. Customizable ratios and specifications.
0.66kV Outdoor Epoxy Cast Busbar-Type Current Transformer for Low Voltage Metering
Outdoor busbar-type current transformer, rated voltage 0.66kV. Designed for low voltage outdoor distribution systems. Rated frequency 50Hz or 60Hz. Ambient temperature range -25°C to +40°C. Compliant with IEC 61869 and GB/T 20840 standards. Outdoor design with weather-resistant construction. Busbar through-core installation, easy to mount on low voltage busbars. Used for current measurement and protection in LV systems.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2070 I is an indoor epoxy resin casting current transformer designed for CGIS gas-insulated switchgear at 35kV. It is available with accuracy classes 0.2FS10, 0.5SFS10, 5P10, 10P10, 5P20 and 10P20. The epoxy casting has an outer diameter of Ø205mm and a through (inner) diameter of Ø70mm for busbar installation, and is rated for 50/60Hz operation. Metering classes (0.2FS10, 0.5SFS10) and protection classes (5P10, 10P10, 5P20, 10P20) cover both measurement and relay protection inside CGIS panels.