LMZK-10 Indoor Open-Core Current Transformer for 10kV Ring Main Unit is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, accuracy class 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P), rated burden 20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P). Design: insulation level 0.72/3kV, Dry Epoxy Resin, 50Hz / 60Hz operation.
LMZK-10 is a 10kV indoor open-core current transformer for ring main units, offering accuracy 0.2/3P(6P) to 1.0/3P(6P) and rated burden up to 120VA. It suits protection and metering in indoor RMU applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZK-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P) | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P) | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 0.72/3kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50Hz / 60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
connect primary through the open core; secondary terminals are 1S1/1S2 for metering, and 2S1/2S2 for protection if dual-winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of LMZK-10?
A: The insulation level is 24/65/125kV: 24kV highest voltage for equipment, 65kV power-frequency withstand, 125kV lightning impulse withstand.
Q: Can LMZK-10 be used outdoors?
A: No, it is designed for indoor use. Outdoor use requires a weatherproof enclosure or special order.
Q: What are the available accuracy classes?
A: Accuracy classes include 0.2/3P(6P), 0.5/3P(6P), and 1.0/3P(6P), suitable for metering and protection.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Parameter | Value |
|---|---|
| Product performance complies with standards | GB/T20840.1, 2 and IEC61869-1, 2 |
| Rated insulation level | 7.2/30/75kV |
| Rated frequency | 50Hz or 60Hz |
| Rated secondary current | 5A or 1A |
| Ambient temperature | -5℃~+40℃ |
Dimension & outline drawing of LMZK-10 — click image to zoom / view original.
The LMZK-10 is an indoor open-core current transformer for 10kV ring main units, designed to step primary current down to a metering or protection signal in accordance with GB/T20840.1, 2 and IEC61869-1, 2. Its dry epoxy resin insulation provides a rated insulation level of 7.2/30/75kV, with creepage and lightning impulse withstand values stated on the nameplate and datasheet.
The secondary is available as 5A or 1A, with accuracy classes 0.2/3P(6P), 0.5/3P(6P) and 1.0/3P(6P) and rated burdens of 20VA(0.2), 75VA(0.5), 120VA(1.0) and 100VA(3P). Choose a single metering core where protection is not required; a metering-plus-protection combination suits feeders needing both; a residual-voltage winding is selected only where earth-fault detection is specified. The secondary circuit must never be open-circuited while energized, and the secondary must be earthed at one point.
Typical indoor deployment covers ring main units in infrastructure such as rail, data centres, hospitals and water works. The unit is rated for -5℃~+40℃. OEM branding and a routine document package are available; ratio and class customization, test reports and delivery terms are quoted on request.
Same product family, different ratings — compare before you specify.
Indoor Open-Core Self-Powered Current Transformer
LMZK-10PU Indoor Open-Core Self-Powered Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, accuracy class 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P), rated burden 20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P). Design: insulation level 18/55/105kV, Dry Epoxy Resin, 50Hz / 60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.