中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLMZK-10
LMZK-10 Indoor Open-Core Current Transformer for 10kV Ring Main Unit
10kVLMZK-10
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2): (0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P))
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LMZK-10

LMZK-10 Indoor Open-Core Current Transformer for 10kV Ring Main Unit

LMZK-10 Indoor Open-Core Current Transformer for 10kV Ring Main Unit is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, accuracy class 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P), rated burden 20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P). Design: insulation level 0.72/3kV, Dry Epoxy Resin, 50Hz / 60Hz operation.

Key Engineering Advantages

  • 10kV open-type split current transformer
  • multiple specifications including waterproof option for ring main unit
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LMZK-10

Electrical Parameters

Primary Rated Voltage (Un):10kV
Metering & Protection Class:0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P)
Rated Output Burden:20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P)
Rated Frequency:50Hz / 60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):0.72/3kV
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

LMZK-10 is a 10kV indoor open-core current transformer for ring main units, offering accuracy 0.2/3P(6P) to 1.0/3P(6P) and rated burden up to 120VA. It suits protection and metering in indoor RMU applications.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLMZK-10Factory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P)Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P)Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)0.72/3kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50Hz / 60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 10kV ring main unit (RMU) applications
  • Indoor switchgear and panel mounting
  • Metering with accuracy class 0.2 or 0.5
  • Protection with class 3P or 6P
  • 50Hz or 60Hz systems

Not Recommended For

  • Outdoor installation (not weatherproof unless specified)
  • Systems above 24kV (insulation level 24/65/125kV)
  • High-accuracy revenue metering requiring class 0.1 or better
  • Gas-insulated switchgear (GIS) without adapter
  • DC or non-sinusoidal applications

Topology & Wiring

connect primary through the open core; secondary terminals are 1S1/1S2 for metering, and 2S1/2S2 for protection if dual-winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of LMZK-10?

A: The insulation level is 24/65/125kV: 24kV highest voltage for equipment, 65kV power-frequency withstand, 125kV lightning impulse withstand.

Q: Can LMZK-10 be used outdoors?

A: No, it is designed for indoor use. Outdoor use requires a weatherproof enclosure or special order.

Q: What are the available accuracy classes?

A: Accuracy classes include 0.2/3P(6P), 0.5/3P(6P), and 1.0/3P(6P), suitable for metering and protection.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LMZK-10
2 cols · 5 rows

LMZK-10 Series Current Transformer — Technical Data

ParameterValue
Product performance complies with standardsGB/T20840.1, 2 and IEC61869-1, 2
Rated insulation level7.2/30/75kV
Rated frequency50Hz or 60Hz
Rated secondary current5A or 1A
Ambient temperature-5℃~+40℃
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LMZK-10 — click image to zoom / view original.

Product Overview

About This Product

LMZK-10

The LMZK-10 is an indoor open-core current transformer for 10kV ring main units, designed to step primary current down to a metering or protection signal in accordance with GB/T20840.1, 2 and IEC61869-1, 2. Its dry epoxy resin insulation provides a rated insulation level of 7.2/30/75kV, with creepage and lightning impulse withstand values stated on the nameplate and datasheet.

The secondary is available as 5A or 1A, with accuracy classes 0.2/3P(6P), 0.5/3P(6P) and 1.0/3P(6P) and rated burdens of 20VA(0.2), 75VA(0.5), 120VA(1.0) and 100VA(3P). Choose a single metering core where protection is not required; a metering-plus-protection combination suits feeders needing both; a residual-voltage winding is selected only where earth-fault detection is specified. The secondary circuit must never be open-circuited while energized, and the secondary must be earthed at one point.

Typical indoor deployment covers ring main units in infrastructure such as rail, data centres, hospitals and water works. The unit is rated for -5℃~+40℃. OEM branding and a routine document package are available; ratio and class customization, test reports and delivery terms are quoted on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LMZK-10PU Indoor Open-Core Self-Powered Current Transformer
10kV
Current Transformer50Hz / 60Hz

LMZK-10PU

Indoor Open-Core Self-Powered Current Transformer

LMZK-10PU Indoor Open-Core Self-Powered Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, accuracy class 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P), rated burden 20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P). Design: insulation level 18/55/105kV, Dry Epoxy Resin, 50Hz / 60Hz operation.

Accuracy Class0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P)
Insulation TypeDry Epoxy Resin
Rated Burden20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P)
View Specs
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS2010

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1765

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs