LMZK-10PU Indoor Open-Core Self-Powered Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, accuracy class 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P), rated burden 20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P). Design: insulation level 18/55/105kV, Dry Epoxy Resin, 50Hz / 60Hz operation.
LMZK-10PU is a self-powered open-core CT for indoor RMU applications, providing protection and metering with a built-in power winding. It suits 15kV systems with insulation level 18/55/105kV.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZK-10PU | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P) | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P) | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 18/55/105kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50Hz / 60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary conductor through the open core. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. The power supply winding terminals are [On Request]. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of LMZK-10PU?
A: The insulation level is 18/55/105kV, meaning 18kV system voltage, power-frequency withstand 55kV, lightning impulse withstand 105kV peak.
Q: How does the self-powered feature work?
A: The built-in power winding generates energy from primary current to power passive protection devices, operating when primary current exceeds 10% of rated.
Q: What accuracy classes are available?
A: Accuracy classes include 0.2/3P, 0.5/3P, and 1.0/3P, with corresponding rated burdens up to 120VA.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated primary current I1n (A) | Accuracy class & rated output (VA) COSφ=0.8 Protection winding10P10 | Accuracy class & rated output (VA) COSφ=0.8 Power supply winding | Dimensions Φd/ΦD/H |
|---|---|---|---|---|
| LMZK1250-10PU | 100/5 | 1 | 5 | 50/124/100 |
| LMZK1150-10PU | 200/5 | 1.5 | 5 | 50/110/100 |
| LMZK1150-10PU | 300/5 | 2.5 | 5 | 50/110/100 |
| LMZK1150-10PU | 400/5 | 3.75 | 5 | 50/110/100 |
| LMZK1150-10PU | 600/5 | 5 | 5 | 50/110/100 |
Dimension & outline drawing of LMZK-10PU — click image to zoom / view original.
The LMZK-10PU is a 10 kV indoor open-core current transformer built around a dry epoxy resin insulation system, a construction choice that removes the liquid-handling and maintenance routines associated with oil-filled units and gives the winding assembly a solid, dimensionally stable body. The epoxy body also supports the unit's 18/55/105 kV insulation level, which defines its power-frequency and lightning-impulse withstand capability for this voltage class.
Accuracy classes 0.2/3P(6P), 0.5/3P(6P) and 1.0/3P(6P) are offered with rated burdens of 20VA(0.2), 75VA(0.5), 120VA(1.0) and 100VA(3P) at 50Hz or 60Hz. A built-in power winding supplies passive microcomputer protection devices, so the open-core design serves metering and protection duties in medium-voltage switchgear, ring-main units and centrally installed cubicles. Compliance follows the IEC 61869 series, with type-test evidence and documentation available [On Request].
This unit is for indoor service only; the secondary circuit must never be open-circuited while the primary is energized. Ratio and accuracy-class customization, sample support and delivery schedules are quoted on request.
Same product family, different ratings — compare before you specify.
Indoor Open-Core Current Transformer for 10kV Ring Main Unit
LMZK-10 Indoor Open-Core Current Transformer for 10kV Ring Main Unit is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, accuracy class 0.2/3P(6P)、0.5/3P(6P)、1.0/3P(6P), rated burden 20VA(0.2),75VA(0.5),120VA(1.0),100VA(3P). Design: insulation level 0.72/3kV, Dry Epoxy Resin, 50Hz / 60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.