Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current:400A、500A、600A、800A、1000A、1200A、1250A; accuracy combinations:0.2S/0.5、0.2S/10P、0.5/10P, rated output:0.2S/0.5S 10VA、0.5 15VA、510P10 15VA、510P15 20/25VA, net weight 19kg, ambient operating temperature -5℃~+40℃.
Indoor 10kV current transformer for medium-voltage switchgear, suitable for metering and protection applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LMZZB5-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
For current transformers, connect primary conductor through the window. Secondary terminals: 1S1-1S2 for metering winding, 2S1-2S2 for protection winding. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 12/42/75kV, meaning 12kV system voltage, 42kV power-frequency withstand, and 75kV lightning impulse withstand.
Q: What are the available primary current ratings?
A: Optional primary currents: 400A, 500A, 600A, 800A, 1000A, 1200A, and 1250A.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) 0.2 (5) | Accuracy class & rated output (VA) 0.5 | Accuracy class & rated output (VA) 10P15 | Accuracy class & rated output (VA) 10P20 | Short-time thermal current (kA) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|
| 20-80 | 0.2(5)/0.5 0.2(5)/0.5/0.5 0.2(5)/10P | 10 | 15 | 20 | 3 | 80/1In | 200/1In | 35 |
| 100 | 0.2(5)/0.5 0.2(5)/0.5/0.5 0.2(5)/10P | 10 | 15 | 20 | 3 | 6 | 15 | 35 |
| 150 | 0.2(5)/0.5 0.2(5)/0.5/0.5 0.2(5)/10P | 10 | 15 | 20 | 3 | 8 | 20 | 35 |
| 200 | 0.2(5)/0.5 0.2(5)/0.5/0.5 0.2(5)/10P | 10 | 15 | 20 | 3 | 12 | 30 | 35 |
| 300 | 0.2(5)/0.5 0.2(5)/0.5/0.5 0.2(5)/10P | 10 | 15 | 20 | 3 | 16 | 40 | 35 |
| 400 | 0.2(5)/0.5 0.2(5)/0.5/0.5 0.2(5)/10P | 10 | 15 | 20 | 3 | 24 | 60 | 35 |
Dimension & outline drawing of LMZZB5-10 — click image to zoom / view original.
The LMZZB5-10 is a 10 kV indoor single-phase epoxy resin cast current transformer, built for revenue metering and protection duties where accuracy directly affects billing settlement. Its dry epoxy resin body insulates the primary and secondary windings, and each unit is routine-tested at the factory, with ratio and polarity checks performed before dispatch.
Accuracy classes 0.2(5), 0.5 and 10P are available, with rated outputs of 10 VA, 15 VA and 20 VA respectively, so the secondary burden can be matched to the connected meters and relays. As an indoor unit it suits switchgear enclosures rather than outdoor service, and it is commonly deployed in heavy-industry distribution for metallurgy, mining, cement and chemical plants. Compliance follows the GB/T 20840 series, with type-test evidence available [On Request].
At commissioning, insulation resistance, polarity and ratio verification should be completed before energising. The secondary must never be open-circuited while the primary is live. DC or non-standard frequencies are outside its scope. Sample and type-test support can be arranged, and ratio or class variants are quoted on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.