LN-0.66 Indoor Low Voltage Current Transformer 0.66kV is designed for metering and protection in power systems. Key ratings: primary voltage 0.66kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.
Indoor LV CT for 0.66kV systems, suitable for measurement and protection in switchgear and panels.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869 / GB/T 20840 |
| Model Code | LN-0.66 | Factory nameplate marking |
| Primary Voltage | 0.66kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | 0.2/0.5/1.0 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869 / GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through the window. Secondary terminals: 1S1 and 1S2 for measurement; if protection winding exists, use 2S1-2S2. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869 / GB/T 20840 for terminal markings.
Compliant with: IEC 61869 / GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the rated primary voltage of this CT?
A: The rated primary voltage is 0.66kV.
Q: What accuracy classes are available?
A: Accuracy classes available are 0.2, 0.5, and 1.0.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated current ratio (A) | Rated output (VA) | Accuracy class | Primary current / turns | Turns through core | Overall dimensions | Aperture dimensions (W×H) | Mounting dimensions (W×H) | ||
|---|---|---|---|---|---|---|---|---|---|---|
| W | D | H | ||||||||
| LMK1-0.66/30 (BH-0.66/30) | 30/5 | 1 | 0.5 | 1 | 1 | 78 | 32 | 78 | 30×30 | 82×31 |
| 40/5 | 1 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 50/5 | 1 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 60/5 | 2 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 75/5 | 2 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 100/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 150/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 200/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 250/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 300/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK1-0.66/40 (BH-0.66/40) | 100/5 | 2.5 | 0.5 | 1 | 1 | 85 | 42 | 78 | 30×30 | 82×31 |
| 150/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 200/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 250/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 300/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK1-0.66/60 (BH-0.66/60) | 300/5 | 5 | 0.5 | 1 | 1 | 90 | 52 | 80 | 30×30 | 82×31 |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK1-0.66/80 (BH-0.66/80) | 400/5 | 5 | 0.5 | 1 | 1 | 105 | 70 | 100 | 40×40 | 82×31 |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK1-0.66/100 (BH-0.66/100) | 600/5 | 5 | 0.5 | 1 | 1 | 120 | 80 | 110 | 50×50 | 82×31 |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 3000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK2-0.66/30 (SDH-0.66/30) | 150/5 | 2.5 | 0.5 | 1 | 1 | 87 | 40 | 100 | 30×30 | 82×30 |
| 200/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 250/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 300/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK2-0.66/40 (SDH-0.66/40) | 200/5 | 2.5 | 0.5 | 1 | 1 | 90 | 45 | 110 | 30×30 | 82×30 |
| 250/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 300/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK2-0.66/60 (SDH-0.66/60) | 400/5 | 5 | 0.5 | 1 | 1 | 102 | 60 | 140 | 40×40 | 82×30 |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK2-0.66/80 (SDH-0.66/80) | 600/5 | 5 | 0.5 | 1 | 1 | 108 | 80 | 150 | 50×50 | 82×30 |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 3000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK3-0.66/30 (LN-0.66/30) | 150/5 | 2.5 | 0.5 | 1 | 1 | 118 | 40 | 120 | 30×30 | 82×30 |
| 200/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 250/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 300/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK3-0.66/40 (LN-0.66/40) | 200/5 | 2.5 | 0.5 | 1 | 1 | 140 | 60 | 120 | 40×40 | 82×30 |
| 250/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 300/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK3-0.66/60 (LN-0.66/60) | 400/5 | 5 | 0.5 | 1 | 1 | 140 | 60 | 120 | 40×40 | 82×30 |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK3-0.66/80 (LN-0.66/80) | 600/5 | 5 | 0.5 | 1 | 1 | 187 | 80 | 120 | 50×50 | 82×30 |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 3000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMK3-0.66/100 (LN-0.66/100) | 1000/5 | 5 | 0.5 | 1 | 1 | 227 | 80 | 120 | 50×50 | 82×30 |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 3000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMZ1-0.66/30 (BH-0.66/30) | 100/5 | 2.5 | 0.5 | 1 | 1 | 248 | 88 | 110 | 30×30 | 228×80 |
| 150/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 200/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 250/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 300/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMZ1-0.66/40 (BH-0.66/40) | 200/5 | 2.5 | 0.5 | 1 | 1 | 270 | 90 | 110 | 30×30 | 228×80 |
| 250/5 | 2.5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 300/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| LMZ1-0.66/60 (BH-0.66/60) | 300/5 | 5 | 0.5 | 1 | 1 | 300 | 100 | 110 | 30×30 | 228×80 |
| 400/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 600/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 750/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 800/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1200/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 1500/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
| 2000/5 | 5 | 0.5 | 1 | 1 | — | — | — | — | — | |
Dimension & outline drawing of LN-0.66 — click image to zoom / view original.
The LN-0.66 is an indoor low-voltage current transformer rated 0.66 kV, used to step primary current down to a 5 A or 1 A secondary for metering and control equipment. Its dry epoxy resin insulation encapsulates the winding, and multiple ratios are available to suit different primary currents.
Accuracy classes 0.2, 0.5 and 1.0 are offered, with rated output in VA to be confirmed on the nameplate or official datasheet. The unit is designed for 50/60 Hz systems and complies with IEC 61869 and GB/T 20840. Type test and routine test documentation can be supplied [On Request].
Typical deployment is in indoor distribution panels, renewable-energy collection stations and energy-storage step-up systems. Secondary terminals should be wired to the meter according to the terminal marking, with the secondary earthed at one point; the secondary must never be open-circuited while energized. The LN-0.66 is not intended for outdoor service or for primary circuits above its rated voltage. Custom ratios and accuracy classes are available, and sample and type-test support can be discussed at enquiry.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.