Three-phase and zero-sequence integrated combination current transformer. Suitable for installation in outdoor circuit breakers or ring main units. Used for three-phase and zero-sequence current measurement and protection. Also applicable for zero-sequence current protection of multi-cable circuits. Compliant with IEC 61869 and GB/T 20840 standards. Epoxy resin cast construction, compact design, easy installation. Integrated three-phase + zero-sequence function saves space and cost.
LSXZ is a 12kV outdoor three-phase integrated CT with zero-sequence, ideal for pole-mounted circuit breakers and RMUs.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869, GB/T 20840 |
| Model Code | LSXZ | Factory nameplate marking |
| Primary Voltage | 12kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A or 1A | Ratio check at rated frequency |
| Accuracy Class | 0.2S, 0.5, 5P20, 5P30 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869, GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Indoor pillar-type epoxy resin cast | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 for measurement, 2S1/2S2 for protection (if applicable). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. For zero-sequence CT, ensure proper polarity and grounding per IEC 61869.
Compliant with: IEC 61869, GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of LSXZ?
A: 12kV system; power-frequency withstand 42kV; lightning impulse withstand 75kV peak.
Q: Can LSXZ be used indoors?
A: No, it is designed for outdoor pole-mounted applications.
Q: What accuracy classes are available?
A: 0.2S, 0.5, 5P20, and 5P30.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Parameter | Value |
|---|---|
| Product performance complies with standards | GB/T20840.1, 2 and IEC61869-1, 2 standards |
| Rated voltage | 0.72/3kV |
| Rated frequency | 50Hz or 60Hz |
| Rated secondary current | 5A or 1A |
| Ambient temperature | -40℃~+60℃ |
| Altitude | Not exceeding 3000m |
| Pollution degree | Class II |
| Rated continuous thermal current | 120%~120% In |
Dimension & outline drawing of LSXZ — click image to zoom / view original.
This is a 12 kV outdoor three-phase integrated current transformer with a zero-sequence core, intended to measure and protect pole-mounted circuit breakers on medium-voltage distribution lines. Its dry epoxy resin cast insulation, rated 12/42/75 kV, forms the solid dielectric body that houses the phase and zero-sequence windings in one unit.
The windings are encapsulated by vacuum casting or automatic pressure gelation, producing a void-free solid insulation structure. Accuracy classes 0.2S, 0.5, 5P20 and 5P30 cover both metering and protection, with secondary outputs of 5 A or 1 A at 50/60 Hz. The rated continuous thermal current is 120% In, and short-time thermal and dynamic withstand figures are available in the datasheet. Standard stocked ratios suit routine switchgear; non-standard ratios and class combinations are built to order.
Compliance follows IEC 61869 and GB/T 20840, supported by datasheets, outline drawings and test reports. Typical deployment is KYN28 medium-voltage switchgear. Observe primary P1/P2 polarity and mount according to the outline drawing; earth the secondary at one point and never open-circuit it while energized. The secondary must never be open-circuited under load. [On Request] for weight and specific short-time ratings.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.