Waterproof zero sequence current transformer, model LXK-Φ120TH. Excellent waterproof performance for humid indoor environments. Rated up to 35kV, 50/60Hz. Split design with waterproof sealing ring, hot-line installation. TH tropicalized design, compliant with IEC 61869 standards. Used for three-phase cable ground fault protection.
Split-core zero sequence CT for earth fault protection, rated up to 35kV, with waterproof and tropicalized design for humid indoor environments.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869, GB/T 20840 |
| Model Code | LXK-120TH | Factory nameplate marking |
| Primary Voltage | Up to 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869, GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Connect the secondary to a protective relay or earth fault detection device. Ensure the primary cable passes through the center and the split core is properly closed and sealed.
Compliant with: IEC 61869, GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the maximum system voltage for this CT?
A: Up to 35kV.
Q: Can it be installed without de-energizing the cable?
A: Yes, it is a split-core design with hot-line installation capability.
Q: Is it suitable for outdoor use?
A: It is designed for humid indoor environments; outdoor use is not specified.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Model | Rated primary current (A) | Accuracy class | Rated output (VA) |
|---|---|---|---|
| LXK-Φ120TH | 50-75/1 | 10P10 | 1.5 |
| LXK-Φ120TH | 100/1 | 10P10 | 3.75 |
| LXK-Φ120TH | 150/1 | 10P10 | 2.5 |
| LXK-Φ120TH | 200-300/1 | 10P10 | 3.75 |
| LXK-Φ120TH | 400-600/1 | 10P10 | 5 |
| LXK-Φ120TH | 100/5 | 10P10 | 2.5 |
| LXK-Φ120TH | 150-200/5 | 10P10 | 2.5 |
| LXK-Φ120TH | 300-400/5 | 10P10 | 3.75 |
| LXK-Φ120TH | 500/5 | 10P10 | 5 |
| LXK-Φ120TH | 600/5 | 10P10 | 5 |
Dimension & outline drawing of LXK-120TH — click image to zoom / view original.
The LXK-120TH is a split-core zero sequence current transformer for earth fault protection on systems up to 35kV, built and tested to IEC 61869 and GB/T 20840. Its dry epoxy resin insulation and split-core construction with sealing ring suit humid indoor environments, where the tropicalized TH finish helps the unit tolerate damp switchgear rooms.
Accuracy class 10P10 is held across the burden range, with rated outputs from 1.5VA to 5VA depending on the selected ratio, covering 50-75/1 through 600/1 and 100/5 through 600/5. The 10P10 class supports consistent error performance from light load toward full burden. Because this is a current transformer, the secondary must never be open-circuited while the primary is energized; short the secondary before breaking the circuit.
This unit is for indoor service only and must not be installed in outdoor exposed locations. Earth the secondary at one point and follow the nameplate terminal diagram. For ratio or accuracy customization, documentation packages and lead times, contact the factory; [On Request] details are available on inquiry.
Same product family, different ratings — compare before you specify.
LXK Φ80 to Φ240 Zero Sequence Current Transformer for Earth Fault Protection
Indoor zero sequence current transformer for 35kV and below systems. Used for three-phase cable ground protection in small grounding current systems. Can also be used with relay protection devices. Rated frequency 50Hz or 60Hz. Available in Φ80 to Φ240 inner diameter sizes. Split design with clamp fastening, can be installed without power interruption. Compliant with IEC 61869 and GB/T 20840 standards. Epoxy resin cast construction, suitable for indoor installation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1765 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.