Indoor zero sequence current transformer for 35kV and below systems. Used for three-phase cable ground protection in small grounding current systems. Can also be used with relay protection devices. Rated frequency 50Hz or 60Hz. Available in Φ80 to Φ240 inner diameter sizes. Split design with clamp fastening, can be installed without power interruption. Compliant with IEC 61869 and GB/T 20840 standards. Epoxy resin cast construction, suitable for indoor installation.
Indoor split-core zero-sequence CT for 35kV systems, ideal for retrofit earth-fault protection on cables without service interruption.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869, GB/T 20840 |
| Model Code | LXK80-240 | Factory nameplate marking |
| Primary Voltage | Up to 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869, GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
For zero-sequence CTs, the three-phase cables must pass through the window together, with the secondary winding connected to a relay or protection device. Terminals are typically marked 1S1 and 1S2; ensure polarity is consistent with the protection scheme. Never open-circuit the secondary of a CT while energized - hazardous voltage may occur. Ground the secondary winding at one point to ensure safety and proper operation.
Compliant with: IEC 61869, GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the maximum system voltage for this CT?
A: It is rated for systems up to 35kV, with insulation level to be confirmed for specific models.
Q: Can it be installed without power interruption?
A: Yes, the split-core design with clamp fastening allows hot-line installation.
Q: What inner diameters are available?
A: The CT is available in Φ80 to Φ240 mm inner diameter sizes.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated current ratio (A) | Accuracy class | Rated output (VA) |
|---|---|---|
| 60-75/1 | 10P5 | 2.5 |
| 100/1 | 10P5 | 3.75 |
| 150/1 | 10P5 | 2.5 |
| 200/1-300/1 | 10P10 | 3.75 |
| 400/1-600/1 | 10P10 | 5 |
| 100/5 | 10P5 | 2.5 |
| 150-200/5 | 10P5 | 2.5 |
| 300/5-400/5 | 10P10 | 3.75 |
| 500/5 | 10P10 | 5 |
| 600/5 | 10P10 | 5 |
Dimension & outline drawing of LXK80-240 — click image to zoom / view original.
This is a dry epoxy resin cast zero sequence current transformer for indoor service up to 35 kV, built to detect earth fault current in three-phase cable ground protection schemes. The cast resin body forms the primary insulation, and the split clamp construction allows the unit to be placed around existing cables without breaking the circuit.
Ratios span 60-75/1 through 600/5, with accuracy classes 10P5 and 10P10 and rated outputs from 2.5 VA to 5 VA depending on the ratio selected. The design follows IEC 61869 and GB/T 20840 at 50/60 Hz. Type and routine test documentation is available [On Request]. Typical deployment is on cable terminations and switchgear intervals in indoor 35 kV substations, where the split core is closed around the cable and the secondary is wired to the earth fault relay.
Secondary terminals must be earthed at one point and the secondary circuit must never be open-circuited while the primary is energized. The unit is for indoor use only and is not suited to harmonic-rich or non-sinusoidal load currents without derating review. Ratio and accuracy combinations are customized to order; the nameplate carries the final ratings.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.