中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZJ-10G
LZJ-10G Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV
0.5kVLZJ-10G
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 0.5kV
Secondary Metering (1S1 - 1S2):5A/1A (0.2/0.5/1.0)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZJ-10G

LZJ-10G Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:20-400A、500-600A、800A、1000A; accuracy combinations 0.2S/10P10、0.5S/10P10 with rated output:0.2S10VA、0.5S10VA、10P10 15VA. Short-time thermal current 60I₁ₙ, dynamic stable current 120I₁ₙ, net weight 15kg, operating ambient temperature -5℃~+40℃.

Key Engineering Advantages

  • 10kV epoxy cast CT
  • integrated metering & protection
  • weight 15kg
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZJ-10G

Electrical Parameters

Primary Rated Voltage (Un):0.5kV
Secondary Winding Currents:5A/1A
Metering & Protection Class:0.2/0.5/1.0
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Standards Conformance:IEC 60044-1 / GB/T 1208
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor 10kV epoxy cast current transformer for metering and protection, rated 0.5kV primary, secondary 5A/1A.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerIEC 60044-1 / GB/T 1208
Model CodeLZJ-10GFactory nameplate marking
Primary Voltage0.5kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class0.2/0.5/1.0Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsIEC 60044-1 / GB/T 1208Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor MV switchgear panels
  • Metering and protection in 10kV systems
  • Epoxy resin insulated environments
  • 50/60Hz networks

Not Recommended For

  • Outdoor installations
  • Gas-insulated switchgear (GIS)
  • High-voltage above 10kV
  • DC systems

Topology & Wiring

secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869 / IEEE C57.13 conventions.

Standards & Compliance

Compliant with: IEC 60044-1 / GB/T 1208

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the primary voltage rating?

A: 0.5kV (system voltage 10kV).

Q: What accuracy classes are available?

A: 0.2/0.5/1.0, with optional 0.2S/10P10 and 0.5S/10P10.

Q: Can it be used outdoors?

A: No, it is designed for indoor use only.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZJ-10G
10 cols · 8 rows

LZJ (C, D)-10G Series Current Transformer

ModelRated primary current I1n (A)Accuracy classCombined0.2(S)0.5(S)10P1010P15Short-time thermal current Ith (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
LZJ-10G20-4000.2(S)/10P10 0.5(S)/10P10101015—60 I1n120 I1n15
LZJ-10G500-6000.2(S)/10P10 0.5(S)/10P10101015—60 I1n120 I1n15
LZJ-10G8000.2(S)/10P10 0.5(S)/10P10101015—60 I1n120 I1n15
LZJ-10G10000.2(S)/10P10 0.5(S)/10P10101015—60 I1n120 I1n15
LZJC-10G LZJD-10G20-4000.2(S)/10P15 0.5(S)/10P151010—1560 I1n120 I1n15
LZJC-10G LZJD-10G500-6000.2(S)/10P15 0.5(S)/10P151010—1560 I1n120 I1n15
LZJC-10G LZJD-10G8000.2(S)/10P15 0.5(S)/10P151010—1560 I1n120 I1n15
LZJC-10G LZJD-10G10000.2(S)/10P15 0.5(S)/10P151010—1560 I1n120 I1n15
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZJ-10G — click image to zoom / view original.

Product Overview

About This Product

LZJ-10G

The LZJ-10G is an indoor single-phase epoxy resin cast current transformer for 10kV systems, used to step primary current down to a 5A/1A secondary for metering and protection. Its design follows IEC 60044-1 and GB/T 1208, with the dry epoxy body providing the primary insulation; dielectric clearances, lightning impulse withstand and partial discharge figures are [On Request].

The unit is offered with accuracy class combinations of 0.2(S)/10P10 and 0.5(S)/10P10, a 10P10 protection core rated at 15 VA, and short-time thermal and dynamic ratings of 60 I1n and 120 I1n respectively, so it holds its accuracy through fault-level currents. Standard stocked ratios cover 20–400 A, 500–600 A, 800 A and 1000 A; non-standard ratios and class pairings are available on request. Typical deployment is in medium-voltage switchgear, ring main units and centre-mounted cubicles.

Secondary wiring must be earthed at one point and the secondary must never be open-circuited while the primary is energised. The 10kV class limits it to indoor service at that level; never apply it above its rated voltage. Weighing 15 kg, it ships with routine test certificates, and a full document package is available on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZJC-10G Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV
10kV
Current Transformer50/60Hz

LZJC-10G

Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV

LZJC-10G Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Accuracy Class0.2/0.5/1.0
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs
LZJD-10G Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV
10kV
Current Transformer50/60Hz

LZJD-10G

Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV

LZJD-10G Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A, accuracy class 0.2S. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Accuracy Class0.2S
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs
CGIS2070 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS2070-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS2070 I is an indoor epoxy resin casting current transformer designed for CGIS gas-insulated switchgear at 35kV. It is available with accuracy classes 0.2FS10, 0.5SFS10, 5P10, 10P10, 5P20 and 10P20. The epoxy casting has an outer diameter of Ø205mm and a through (inner) diameter of Ø70mm for busbar installation, and is rated for 50/60Hz operation. Metering classes (0.2FS10, 0.5SFS10) and protection classes (5P10, 10P10, 5P20, 10P20) cover both measurement and relay protection inside CGIS panels.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs