中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZ9-10
LZZ9-10 Indoor Single-phase Epoxy Resin Casting Current Transformer
10kVLZZ9-10
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2):5A / 1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZ9-10

LZZ9-10 Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZ9-10 Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A / 1A. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50Hz / 60Hz operation.

Key Engineering Advantages

  • Customized for SF6 switchgear
  • excellent short-time thermal and dynamic current resistance performance
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZ9-10

Electrical Parameters

Primary Rated Voltage (Un):10kV
Secondary Winding Currents:5A / 1A
Rated Frequency:50Hz / 60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):12/42/75kV
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor CT for 10kV systems, ideal for SF6 switchgear, with 5A/1A secondary and dry epoxy insulation.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLZZ9-10Factory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current5A / 1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)12/42/75kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50Hz / 60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 10kV indoor switchgear and RMU
  • SF6 gas-insulated switchgear
  • Metering and protection applications
  • 50Hz or 60Hz systems

Not Recommended For

  • Outdoor installations
  • Systems above 10kV
  • Gas-insulated primary (not SF6) applications
  • High-altitude or polluted environments without derating

Topology & Wiring

Connect primary in series with the line. Secondary terminals: 1S1 and 1S2 for metering, 2S1 and 2S2 for protection if present. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of this CT?

A: The insulation level is 0.72/3kV, meaning 0.72kV system voltage and 3kV power-frequency withstand.

Q: Can this CT be used outdoors?

A: No, it is designed for indoor use, specifically for SF6 switchgear.

Q: What standards does it comply with?

A: It complies with GB/T20840.1, GB/T20840.2, IEC61869-1, and IEC61869-2.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZ9-10
7 cols · 1 rows

LZZ9-10 Current Transformer

Rated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA) COSφ=0.8 (0.2 (S))Accuracy class & rated output (VA) COSφ=0.8 (0.5 (S))Short-time thermal current Ith (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
20-1500.2(S) 0.5(S) 0.2S/0.2101060I1n150I1n20
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZ9-10 — click image to zoom / view original.

Product Overview

About This Product

LZZ9-10

This is an indoor single-phase epoxy resin cast current transformer for 10kV medium-voltage switchgear, stepping primary current down to a 5A or 1A secondary for metering and protection in KYN28, ring-main and substation bays. The dry epoxy body insulates the primary from the secondary and earth, with the metering and protection windings cast in place; the winding arrangement for each accuracy class is shown on the nameplate terminal diagram.

Accuracy class 0.2 with a 10VA rated burden at 50Hz or 60Hz supports revenue metering, while the short-time thermal and dynamic current resistance is intended for fault-level duty in SF6 switchgear. The 12/42/75kV insulation level suits 10kV indoor service. Selection within the family turns on ratio, accuracy class and winding configuration; the datasheet and nameplate give the ratings for each variant.

Compliance evidence and test reports are available [On Request]. The unit is for indoor installation only; never exceed the 10kV class. Earth the secondary at one point and never open-circuit it while energized. Ratio, accuracy class and winding configuration can be customized, and the document package is quoted on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs