中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZB-10
LZZB-10 Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV
10kVLZZB-10
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2):5A/1A (5P/10P)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZB-10

LZZB-10 Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV

LZZB-10 Indoor Single-phase Epoxy Resin Casting Current Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A/1A, accuracy class 5P/10P. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Key Engineering Advantages

  • 10kV epoxy cast CT
  • compact structure
  • weight 17kg
  • dual functions of metering and protection
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZB-10

Electrical Parameters

Primary Rated Voltage (Un):10kV
Secondary Winding Currents:5A/1A
Metering & Protection Class:5P/10P
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Standards Conformance:IEC 61869 / GB/T 20840
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor 10kV epoxy cast current transformer for metering and protection in MV switchgear. Suitable for 50/60Hz systems with secondary 5A or 1A.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerIEC 61869 / GB/T 20840
Model CodeLZZB-10Factory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class5P/10PAccuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsIEC 61869 / GB/T 20840Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium-voltage switchgear panels
  • Revenue metering with accuracy 0.2S/0.5S
  • Protection applications with 5P/10P class
  • 10kV class systems (Um=12kV)
  • Ambient temperatures -5°C to +40°C

Not Recommended For

  • Outdoor installations (indoor type only)
  • Gas-insulated switchgear (GIS) without adaptation
  • High-voltage systems above 12kV
  • DC applications
  • High-altitude installations above 1000m (unless derated)

Topology & Wiring

Connect primary through bushing. Secondary terminals: 1S1-1S2 for metering, 2S1-2S2 for protection (if present). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: IEC 61869 / GB/T 20840

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of this CT?

A: The insulation level is 12/42/75kV, meaning 12kV highest voltage for equipment, 42kV power-frequency withstand, and 75kV lightning impulse withstand.

Q: Can this CT be used outdoors?

A: No, it is designed for indoor use only, as it is an indoor single-phase epoxy resin casting type.

Q: What accuracy classes are available?

A: It offers accuracy combinations of 0.2S/10P and 0.5S/10P, suitable for both metering and protection.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZB-10
8 cols · 4 rows

LZZB-10 Current Transformer

Rated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA) COSΦ=0.8 0.2 (S)Accuracy class & rated output (VA) COSΦ=0.8 0.5 (S)Accuracy class & rated output (VA) COSΦ=0.8 10P10Short-time thermal current Ith (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
20-2000.2(S)/10P101015150 I1n375 I1n17
300-4000.2(S)/10P10101545112.517
500-6000.5(S)/10P1010156015017
600-8000.5(S)/10P1010156015017
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZB-10 — click image to zoom / view original.

Product Overview

About This Product

LZZB-10

This is an indoor single-phase epoxy resin cast current transformer for 10kV switchgear, typically installed in KYN28 metal-clad cubicles, ring-main units and substation bays to step primary current down to 5A/1A for metering and protection. Its dry-type insulation is a cast epoxy body rather than an oil or gas dielectric, and the windings and insulation are encapsulated together to form a solid, gapless insulation system.

The LZZB-10 is rated for 50/60Hz service with accuracy classes 5P/10P, and the parameter table lists 0.2(S) or 0.5(S) metering classes with 10VA output and a 10P10 protection output of 15VA. Short-time thermal current and dynamic stability follow the primary current selected; the unit weighs 17kg. Compared with oil-immersed or SF6 designs, the casting avoids liquid handling and gas supervision, which suits indoor cubicle installation. It is built to IEC 61869 and GB/T 20840, with routine and type test documentation available [On Request].

Secondary terminals are marked per the nameplate; earth the secondary at one point and never open-circuit it while energized. Specify ratio, class and winding configuration at enquiry; [On Request] covers test reports and delivery.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZZB1-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV
10kV
Current Transformer50/60Hz

LZZB1-10

Indoor Single-phase Epoxy Cast Current Transformer 10kV

LZZB1-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Accuracy Class0.2/0.5/1.0
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs
LZZB2-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV
10kV
Current Transformer50/60Hz

LZZB2-10

Indoor Single-phase Epoxy Cast Current Transformer 10kV

LZZB2-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A/1A, accuracy class 0.2/0.5. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Accuracy Class0.2/0.5
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs
LZZB-27.5 Indoor Single-phase Epoxy Resin Casting Current Transformer
10kV
Current Transformer50/60Hz

LZZB-27.5

Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2、IEC61869-1/2 and JB/T8510.1-2007 standards; rated insulation level 31.5/95/185kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Optional primary current covers 10-2000A; accuracy-class rated outputs range 10-60VA for grades 0.2S,0.5S,0.2,0.5,5P10,5P15,5P20; short-time thermal current ranges 15-100kA, rated dynamic stable current ranges 37.5-200kA; product weight:85kg; ambient operating temperature -5℃~+40℃.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs