中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZB-27.5
LZZB-27.5 Indoor Single-phase Epoxy Resin Casting Current Transformer
10kVLZZB-27.5
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2):5A/1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZB-27.5

LZZB-27.5 Indoor Single-phase Epoxy Resin Casting Current Transformer

Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2、IEC61869-1/2 and JB/T8510.1-2007 standards; rated insulation level 31.5/95/185kV, rated frequency 50/60Hz, rated secondary current 5A or 1A. Optional primary current covers 10-2000A; accuracy-class rated outputs range 10-60VA for grades 0.2S,0.5S,0.2,0.5,5P10,5P15,5P20; short-time thermal current ranges 15-100kA, rated dynamic stable current ranges 37.5-200kA; product weight:85kg; ambient operating temperature -5℃~+40℃.

Key Engineering Advantages

  • 27.5kV indoor epoxy cast current transformer
  • abundant current grades & accuracy classes
  • excellent thermal and dynamic stability
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZB-27.5

Electrical Parameters

Primary Rated Voltage (Un):10kV
Secondary Winding Currents:5A/1A
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):12/42/75kV
Environmental Class:Ambient: -5℃~+40℃
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

LZZB-27.5 is a 27.5kV indoor epoxy cast current transformer, suitable for medium voltage switchgear applications. It is not for outdoor or high voltage transmission use.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLZZB-27.5Factory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)12/42/75kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentAmbient: -5℃~+40℃Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium voltage switchgear panels
  • Metering and protection in 27.5kV systems
  • Applications requiring high accuracy classes (0.2S, 0.5S)
  • Environments with ambient temperatures -5°C to +40°C

Not Recommended For

  • Outdoor installations without additional enclosure
  • High voltage transmission systems above 27.5kV
  • DC systems or non-standard frequencies
  • Applications requiring gas or oil insulation

Topology & Wiring

Connect primary terminals in series with the line. Secondary terminals are 1S1 and 1S2 for the main winding; if a protection winding is present, use 2S1 and 2S2. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Ensure correct polarity for metering and protection.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of this CT?

A: The insulation level is 12/42/75kV, meaning 12kV system voltage, 42kV power-frequency withstand, and 75kV lightning impulse withstand.

Q: What secondary currents are available?

A: The secondary current can be 5A or 1A.

Q: What accuracy classes are offered?

A: Accuracy classes include 0.2S, 0.5S, 0.2, 0.5, 5P10, 5P15, and 5P20.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZB-27.5
6 cols · 9 rows

LZZB-27.5 Current Transformer

Rated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA)COSφ=0.5Short-time thermal current Ith (kA/S)Rated dynamic current Idyn (kA)Weight (kg)
10-500.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P10 10 15 20 50 30 20150 1in375 1in85
750.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P10 10 15 20 50 30 201537.585
1000.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P10 10 15 20 50 30 20257585
1500.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P10 10 15 20 50 30 2031.58085
200-2500.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P10 10 15 20 50 30 2045112.585
300-5000.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P10 10 15 20 50 30 205012585
600-6300.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P10 10 15 20 50 30 206313085
750-10000.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P15 15 20 30 60 40 308018085
1200-20000.2(S)/0.2(S) 0.2(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P15 15 20 30 60 40 3010020085
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZB-27.5 — click image to zoom / view original.

Product Overview

About This Product

LZZB-27.5

The LZZB-27.5 is a 27.5 kV indoor single-phase epoxy resin cast current transformer, typically installed in switchgear bays and ring-main compartments to step primary current down to 5 A or 1 A for metering and protection. Its dry epoxy body replaces oil or SF6 insulation, reducing maintenance and fire risk, while the casting and winding process is supported by routine factory checks including ratio and polarity verification and dielectric screening.

Accuracy classes span 0.2(S) and 0.5(S) metering and 5P protection, with rated outputs from 10 VA to 60 VA depending on class and ratio; short-time thermal current reaches 100 kA for 1 s and dynamic stability 200 kA at the higher ratios, with a weight of 85 kg. The design follows IEEE C57.13 practice, and type-test reports and routine test certificates are available [On Request].

It suits indoor distribution in metallurgical, mining, cement and chemical plants. Before energizing, verify secondary burden against the rated VA and earth the secondary at one point; never open-circuit the secondary while energized. This indoor unit is not for outdoor installation. Custom ratios, accuracy classes and sample or type-test support are quoted on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZZB3-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV
10kV
Current Transformer50/60Hz

LZZB3-10

Indoor Single-phase Epoxy Cast Current Transformer 10kV

LZZB3-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A, accuracy class 0.2S/0.5S/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Accuracy Class0.2S/0.5S/0.5/1.0
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs
LZZB8-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer
35kV
Current Transformer50/60Hz

LZZB8-35-Q

Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZB8-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZB8-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
LZZB9-12-35-168-CGIS Current Transformer for CGIS Gas Insulated Switchgear
12kV/35kV
Current Transformer50Hz / 60Hz

LZZB9-12-35-168-CGIS

Current Transformer for CGIS Gas Insulated Switchgear

LZZB9-12-35-168-CGIS Current Transformer for CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 12kV/35kV, secondary voltage 5A or 1A. Design: insulation level 12/42/75, 40.5/95/185kV, Dry Epoxy Resin, 50Hz / 60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs