KEMA & ISO 9001/14001 Certified|Exporting to 50+ Countries (IEC 61869-3 / IEEE C57.13)
24/7 Global Engineering Hotline: 86 18852046268|sales@potentialtransformers.com
中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZB8-35-Q
LZZB8-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer
35kVLZZB8-35-Q
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 35kV
Secondary Metering (1S1 - 1S2):5A/1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZB8-35-Q

LZZB8-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZB8-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZB8-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • 35kV indoor epoxy cast current transformer
  • customizable configuration
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZB8-35-Q

Electrical Parameters

Primary Rated Voltage (Un):35kV
Secondary Winding Currents:5A/1A
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):40.5/95/185kV
Environmental Class:Ambient: -5℃~+40℃
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

Indoor 35kV epoxy cast current transformer for medium-voltage switchgear, suitable for metering and protection up to 2500A primary.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLZZB8-35-QFactory nameplate marking
Primary Voltage35kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)40.5/95/185kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentAmbient: -5℃~+40℃Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium-voltage switchgear panels
  • Revenue metering and protection applications
  • Systems up to 40.5kV (Um) with 95kV power-frequency and 185kV lightning impulse withstand
  • Primary currents from 20A to 2500A with 5A or 1A secondary output

Not Recommended For

  • Outdoor installations (indoor type only)
  • Gas-insulated switchgear (GIS) without adaptation
  • DC systems or non-sinusoidal waveforms
  • High-altitude environments above 1000m (unless derated)

Topology & Wiring

For current transformers, connect primary terminals P1/P2 in series with the line. Secondary terminals are 1S1/1S2 for the main winding; if a protection winding exists, use 2S1/2S2. Never open-circuit the secondary of a CT while energized – hazardous voltage may occur. Ground the secondary circuit at one point only to avoid circulating currents. Follow IEC 61869-2 terminal markings and ensure shorting before disconnecting.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of this CT?

A: The rated insulation level is 40.5kV system voltage, with power-frequency withstand of 95kV and lightning impulse withstand of 185kV peak.

Q: Can this CT be used outdoors?

A: No, it is designed for indoor use only due to its epoxy resin casting and indoor construction.

Q: What secondary currents are available?

A: The secondary current is either 5A or 1A, as specified.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZB8-35-Q
10 cols · 9 rows

LZZBJ9-35A LZZQB8-35A LZZB8-35 (Q) Current Transformer

Rated primary current I1n (A)Accuracy classCombinedRated output (VA) 0.2 (S)/0.5SRated output (VA) 0.5Rated output (VA) 5P10Rated output (VA) 5P15Short-time thermal current Ith (kA/S) kAShort-time thermal current Ith (kA/S) sRated dynamic current Idyn (kA)Weight (kg)
200.2/0.5 0.2/5P 0.5/5P10153020411070
30-400.2/0.5 0.2/5P 0.5/5P10153020421070
500.2/0.5 0.2/5P 0.5/5P101530201213070
750.2/0.5 0.2/5P 0.5/5P101530201614070
100-1500.2/0.5 0.2/5P 0.5/5P101530202516370
200-3000.2/0.5 0.2/5P 0.5/5P1015302031.518070
400-6000.2/0.5 0.2/5P 0.5/5P1015302031.528070
800-16000.2/0.5 0.2/5P 0.5/5P1015302031.548070
2000-25000.2/0.5 0.2/5P 0.5/5P1015302031.5413070
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZB8-35-Q — click image to zoom / view original.

Product Overview

About This Product

LZZB8-35-Q

The LZZB8-35(Q) is a 35 kV indoor single-phase epoxy resin cast current transformer, engineered for revenue metering and protection in medium-voltage distribution systems. Its accuracy classes of 0.2, 0.5 and 5P, with a rated burden of 10 VA, support precise energy accounting and dependable fault detection.

Dry epoxy resin casting provides the primary insulation, with a rated insulation level of 40.5/95/185 kV, suitable for 50/60 Hz operation. The design is intended for indoor service within an ambient range of -5℃ to +40℃; for any environmental protection figures beyond this, refer to the nameplate or official datasheet [On Request].

Short-time thermal and dynamic ratings scale with primary current, reaching 31.5 kA and 80 kA respectively at higher ratings, with a unit weight of 70 kg. Compliance follows the GB/T 20840 series. Typical deployment includes heavy-industry distribution in metallurgy, mining, cement and chemical plants. Before energizing, perform insulation resistance, polarity and ratio checks, earth the secondary at one point, and never open-circuit the secondary while energized. Custom ratios and accuracy classes are available; contact the factory for lead times and documentation.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs