LZZB8-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZB8-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor 35kV epoxy cast current transformer for medium-voltage switchgear, suitable for metering and protection up to 2500A primary.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZB8-35-Q | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 40.5/95/185kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
For current transformers, connect primary terminals P1/P2 in series with the line. Secondary terminals are 1S1/1S2 for the main winding; if a protection winding exists, use 2S1/2S2. Never open-circuit the secondary of a CT while energized – hazardous voltage may occur. Ground the secondary circuit at one point only to avoid circulating currents. Follow IEC 61869-2 terminal markings and ensure shorting before disconnecting.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The rated insulation level is 40.5kV system voltage, with power-frequency withstand of 95kV and lightning impulse withstand of 185kV peak.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only due to its epoxy resin casting and indoor construction.
Q: What secondary currents are available?
A: The secondary current is either 5A or 1A, as specified.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Rated output (VA) 0.2 (S)/0.5S | Rated output (VA) 0.5 | Rated output (VA) 5P10 | Rated output (VA) 5P15 | Short-time thermal current Ith (kA/S) kA | Short-time thermal current Ith (kA/S) s | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 4 | 1 | 10 | 70 |
| 30-40 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 4 | 2 | 10 | 70 |
| 50 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 12 | 1 | 30 | 70 |
| 75 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 16 | 1 | 40 | 70 |
| 100-150 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 25 | 1 | 63 | 70 |
| 200-300 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 31.5 | 1 | 80 | 70 |
| 400-600 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 31.5 | 2 | 80 | 70 |
| 800-1600 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 31.5 | 4 | 80 | 70 |
| 2000-2500 | 0.2/0.5 0.2/5P 0.5/5P | 10 | 15 | 30 | 20 | 31.5 | 4 | 130 | 70 |
Dimension & outline drawing of LZZB8-35-Q — click image to zoom / view original.
The LZZB8-35(Q) is a 35 kV indoor single-phase epoxy resin cast current transformer, engineered for revenue metering and protection in medium-voltage distribution systems. Its accuracy classes of 0.2, 0.5 and 5P, with a rated burden of 10 VA, support precise energy accounting and dependable fault detection.
Dry epoxy resin casting provides the primary insulation, with a rated insulation level of 40.5/95/185 kV, suitable for 50/60 Hz operation. The design is intended for indoor service within an ambient range of -5℃ to +40℃; for any environmental protection figures beyond this, refer to the nameplate or official datasheet [On Request].
Short-time thermal and dynamic ratings scale with primary current, reaching 31.5 kA and 80 kA respectively at higher ratings, with a unit weight of 70 kg. Compliance follows the GB/T 20840 series. Typical deployment includes heavy-industry distribution in metallurgy, mining, cement and chemical plants. Before energizing, perform insulation resistance, polarity and ratio checks, earth the secondary at one point, and never open-circuit the secondary while energized. Custom ratios and accuracy classes are available; contact the factory for lead times and documentation.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.