中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZB1-10
LZZB1-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV
10kVLZZB1-10
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2):5A/1A (0.2/0.5/1.0)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZB1-10

LZZB1-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV

LZZB1-10 Indoor Single-phase Epoxy Cast Current Transformer 10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Key Engineering Advantages

  • 10kV epoxy cast CT
  • weight 15kg
  • metering & protection combined
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZB1-10

Electrical Parameters

Primary Rated Voltage (Un):10kV
Secondary Winding Currents:5A/1A
Metering & Protection Class:0.2/0.5/1.0
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Standards Conformance:IEC 61869 / GB/T 20840
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

LZZB1-10 is a 10kV indoor epoxy cast current transformer for metering and protection, suitable for medium voltage switchgear panels.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent TransformerIEC 61869 / GB/T 20840
Model CodeLZZB1-10Factory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class0.2/0.5/1.0Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
StandardsIEC 61869 / GB/T 20840Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor medium voltage switchgear (RMU, panel boards)
  • Metering and protection applications up to 10kV
  • Revenue metering with accuracy class 0.2S
  • Protection with class 5P10
  • 50/60Hz systems

Not Recommended For

  • Outdoor installation (not weatherproof)
  • High voltage transmission (above 10kV)
  • DC systems
  • High current primary (above 800A)
  • Gas-insulated switchgear (GIS) without adaptation

Topology & Wiring

Connect primary through the bushing. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: IEC 61869 / GB/T 20840

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the insulation level of LZZB1-10?

A: The insulation level is 12/42/75kV, meaning 12kV highest voltage for equipment, 42kV power-frequency withstand, 75kV lightning impulse withstand.

Q: What are the available accuracy classes?

A: Accuracy classes include 0.2S/0.2S, 0.2S/0.5S, and 0.2S/5P10, with rated output 15VA per class.

Q: Can it be used for outdoor applications?

A: No, it is designed for indoor use only, as it is epoxy cast and not weatherproof.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZB1-10
6 cols · 5 rows

LZZBJ1-10, LZZBJ2-10, LZZBJ3-10 Current Transformer — Technical Data

Rated primary current (A)Accuracy classCombinedAccuracy class & rated output (VA)Short-time thermal current (kA/S)Rated dynamic current (kA)Weight (kg)
200.2/5(0.2/5) 0.2/5(0.5/5) 0.5/5(0.5/5) 0.5/5(10P/10)15100250—
300—152460—
400—15328015
500—1540100—
600-800—1548120—
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZB1-10 — click image to zoom / view original.

Product Overview

About This Product

LZZB1-10

The LZZB1-10 is an indoor single-phase epoxy cast current transformer for 10kV systems, designed to step primary current down to 5A or 1A for metering and protection. It follows IEC 61869 and GB/T 20840, placing it within a recognised framework for routine and type testing.

Its dry epoxy resin body encapsulates the windings, and factory checks include routine tests, ratio and polarity verification, with partial discharge screening available [On Request]. Accuracy classes 0.2, 0.5 and 1.0 are offered with a 15VA rated burden, and the secondary is available as 5A or 1A to suit different relay and meter inputs. Within the range, the choice between accuracy classes and secondary currents depends on the burden and metering or protection requirements; this unit combines both functions. A full document package including datasheet, outline drawing and test reports can be supplied.

Typical deployment is in indoor distribution boards for heavy industry such as metallurgy, mining, cement and chemical plants. Earth the secondary at one point and bond it equipotentially; never open-circuit the secondary while energised. Custom ratios and accuracy classes are available, and export packing with after-sales support is offered; weight is 15kg.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs