LZZB(J)7-35(Q) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZB-J7-35-Q) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A/1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor 35kV class current transformer for medium voltage switchgear; suitable for protection and metering in indoor applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZB-J7-35-Q | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 40.5/95/185kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
For current transformer: connect primary in series with the line. Secondary terminals: 1S1/1S2 for metering, 2S1/2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal conventions.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 40.5kV system; power-frequency withstand 95kV; lightning impulse withstand 185kV peak.
Q: What are the available secondary currents?
A: Secondary current is 5A or 1A.
Q: Can this CT be used outdoors?
A: No, it is designed for indoor use only.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Rated secondary output (VA) | Short-time thermal current Ith (kA) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 20 | 0.2/0.5(0.5)/0.5 0.5/0.5/0.5 0.2/0.5/0.5 0.2/0.5/0.5 | 15 15 25 | 1.3 | 3.25 | 95 |
| 30 | — | — | 2 | 5 | — |
| 40 | — | — | 3 | 7.5 | — |
| 50 | — | — | 4.5 | 11.5 | — |
| 75 | — | — | 6 | 15 | — |
| 100 | — | — | 8 | 22.5 | — |
| 150 | — | — | 12 | 30 | — |
| 200 | — | — | 16 | 45 | — |
| 300 | — | — | 20 | 50 | — |
| 400 | — | — | 25 | 63 | — |
| 500 | — | — | 36 | 90 | — |
| 600 | — | — | 40 | 100 | — |
| 800 | — | — | 50 | 125 | — |
| 1000-1500 | — | — | 63 | 160 | — |
| 1500-2000 | — | — | 80 | 200 | — |
Dimension & outline drawing of LZZB-J7-35-Q — click image to zoom / view original.
This 35 kV indoor single-phase current transformer is specified within the IEC 61869, GB/T 20840 and IEEE C57.13 framework, stepping primary current down to 5 A or 1 A for metering and protection in medium-voltage switchgear. Its dry epoxy resin body is vacuum cast to form a solid, air-gap-free insulation around the core and windings, available in two-winding or three-winding configurations.
Accuracy is 0.2(S) for metering and 10P10 for protection, with rated outputs of 15 VA and 25 VA; at 20 A primary the short-time thermal current is 1.3 kA and dynamic stability 3.25 kA, and the unit weighs 95 kg. Insulation level is 40.5/95/185 kV at 50/60 Hz, and the design suits indoor switchgear and ring-main units rather than fused outdoor schemes. Datasheets, outline drawings and routine test reports are available [On Request].
Primary connections follow the P1/P2 markings, with the secondary earthed at one point and the circuit never opened while energized; pre-energization checks follow the nameplate. DC or non-standard frequencies are not applicable, and ambient must stay within -5℃~+40℃. Ratio and accuracy combinations are customized to order, with documentation packages quoted on request. ⚠️ Safety: Never open-circuit the secondary of a CT while energized — hazardous voltage develops.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer,10kV
LZZBJ9-10 Indoor Single-phase Epoxy Resin Casting Current Transformer,10kV is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.
10kV Indoor Epoxy Cast Current Transformer for KYN28 Cabinet
LZZBJ9-10GWA,B,C 10kV Indoor Epoxy Cast Current Transformer for KYN28 Cabinet (LZZBJ9-10GWA-B-C) is designed for metering and protection in power systems. Key ratings: primary voltage 10kV, secondary voltage 5A or 1A, accuracy class 0.2S, 0.5, 5P20, 5P30. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869, GB/T 20840.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-12/135b/4s Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-12-135b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation.