Indoor single-phase epoxy resin casting current transformer dedicated for solid insulation ring main unit, complying with GB/T20840.1, GB/T20840.2, IEC61869-1 and IEC61869-2 standards.
LZZBJ15-10GT is a 10kV indoor current transformer for solid insulation ring main units, ideal for protection and metering in compact switchgear.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ15-10GT | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | 1P10 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | 10 VA / 15 VA | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
For CT secondary terminals: use 1S1/1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point per IEC 61869-2.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the primary voltage rating?
A: The primary voltage is 10kV.
Q: What standards does it comply with?
A: It complies with GB/T20840.1, GB/T20840.2, IEC61869-1 and IEC61869-2.
Q: Is it suitable for outdoor use?
A: No, it is designed for indoor use in solid insulation ring main units.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA)COSφ=0.8 0.2 | Accuracy class & rated output (VA)COSφ=0.8 0.5 | Accuracy class & rated output (VA)COSφ=0.8 10P15 | Short-time thermal current Ith (kA/S) | Rated dynamic current Idyn (kA) |
|---|---|---|---|---|---|---|
| 50-200 | 0.2/0.5/10P | 10 | 10 | 10 | 80 1in | 200 1in |
| 300-400 | 0.2/0.5/10P | 10 | 10 | 10 | 25 | 62.5 |
| 500-600 | 0.2/0.5/10P | 10 | 10 | 15 | 31.5 | 80 |
| 800 | 0.2/0.5/10P | 10 | 10 | 15 | 45 | 100 |
| 1000-1250 | 0.2/0.5/10P | 10 | 10 | 15 | 63 | 130 |
Dimension & outline drawing of LZZBJ15-10GT — click image to zoom / view original.
This is an indoor single-phase epoxy resin cast current transformer for 10 kV systems, designed to step primary current down to a measurable secondary level for protection and metering in solid insulation ring cabinets. Its dry epoxy resin body replaces oil or gas insulation, so the unit is compact and suited to enclosed switchgear where liquid maintenance is not wanted.
Electrical performance is defined by accuracy class 1P10 with rated outputs of 10 VA and 15 VA at 50/60 Hz, and the design provides strong short-time thermal and dynamic current endurance. Standard production covers ratio ranges from 50-200 A up to 1000-1250 A, with short-time thermal current from 25 kA to 80 kA and dynamic current from 62.5 kA to 200 kA depending on the row. Non-standard ratios and accuracy combinations are available [On Request].
The secondary circuit must never be open-circuited while the primary is energized. Install indoors only, respecting the clearance and fixing dimensions on the outline drawing, earth the secondary at one point, and verify ratio and polarity before commissioning. Type test and routine test documentation, calibration certificates and sample support are available on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.