中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZBJ15-10GT
LZZBJ15-10GT Indoor Single-phase Epoxy Resin Casting Current Transformer for Solid Insulation Ring Cabinet
10kVLZZBJ15-10GT
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 10kV
Secondary Metering (1S1 - 1S2): (1P10)
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZBJ15-10GT

LZZBJ15-10GT Indoor Single-phase Epoxy Resin Casting Current Transformer for Solid Insulation Ring Cabinet

Indoor single-phase epoxy resin casting current transformer dedicated for solid insulation ring main unit, complying with GB/T20840.1, GB/T20840.2, IEC61869-1 and IEC61869-2 standards.

Key Engineering Advantages

  • Special design for solid insulation ring cabinet
  • strong short-time thermal and dynamic current endurance
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZBJ15-10GT

Electrical Parameters

Primary Rated Voltage (Un):10kV
Metering & Protection Class:1P10
Rated Output Burden:10 VA / 15 VA
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

LZZBJ15-10GT is a 10kV indoor current transformer for solid insulation ring main units, ideal for protection and metering in compact switchgear.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLZZBJ15-10GTFactory nameplate marking
Primary Voltage10kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class1P10Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden10 VA / 15 VABurden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • 10kV solid insulation ring main units (RMU)
  • Indoor switchgear applications
  • Protection and metering circuits
  • 50/60Hz power systems

Not Recommended For

  • Outdoor substations
  • Gas-insulated switchgear (GIS) without adaptation
  • High-voltage transmission networks (>10kV)
  • Applications requiring oil or SF6 insulation

Topology & Wiring

For CT secondary terminals: use 1S1/1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point per IEC 61869-2.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the primary voltage rating?

A: The primary voltage is 10kV.

Q: What standards does it comply with?

A: It complies with GB/T20840.1, GB/T20840.2, IEC61869-1 and IEC61869-2.

Q: Is it suitable for outdoor use?

A: No, it is designed for indoor use in solid insulation ring main units.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZBJ15-10GT
7 cols · 5 rows

LZZBJ15-10GT Current Transformer

Rated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA)COSφ=0.8 0.2Accuracy class & rated output (VA)COSφ=0.8 0.5Accuracy class & rated output (VA)COSφ=0.8 10P15Short-time thermal current Ith (kA/S)Rated dynamic current Idyn (kA)
50-2000.2/0.5/10P10101080 1in200 1in
300-4000.2/0.5/10P1010102562.5
500-6000.2/0.5/10P10101531.580
8000.2/0.5/10P10101545100
1000-12500.2/0.5/10P10101563130
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZBJ15-10GT — click image to zoom / view original.

Product Overview

About This Product

LZZBJ15-10GT

This is an indoor single-phase epoxy resin cast current transformer for 10 kV systems, designed to step primary current down to a measurable secondary level for protection and metering in solid insulation ring cabinets. Its dry epoxy resin body replaces oil or gas insulation, so the unit is compact and suited to enclosed switchgear where liquid maintenance is not wanted.

Electrical performance is defined by accuracy class 1P10 with rated outputs of 10 VA and 15 VA at 50/60 Hz, and the design provides strong short-time thermal and dynamic current endurance. Standard production covers ratio ranges from 50-200 A up to 1000-1250 A, with short-time thermal current from 25 kA to 80 kA and dynamic current from 62.5 kA to 200 kA depending on the row. Non-standard ratios and accuracy combinations are available [On Request].

The secondary circuit must never be open-circuited while the primary is energized. Install indoors only, respecting the clearance and fixing dimensions on the outline drawing, earth the secondary at one point, and verify ratio and polarity before commissioning. Type test and routine test documentation, calibration certificates and sample support are available on request.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1911

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1775

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs