LZZBJ18-35G3-175-CGIS Indoor Single-phase Epoxy Resin Casting Current Transformer is designed for metering and protection in power systems. Key ratings: primary voltage 35kV, secondary voltage 5A or 1A. Design: insulation level 40.5/95/185kV, Dry Epoxy Resin, 50Hz / 60Hz operation.
Indoor epoxy resin CT for 10kV systems, suitable for CGIS switchgear with metering and protection applications.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ18-35G3-175-CGIS | Factory nameplate marking |
| Primary Voltage | 35kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A or 1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 40.5/95/185kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50Hz / 60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary terminals P1/P2 in series with the line. Secondary terminals are 1S1/1S2 for metering winding, and 2S1/2S2 for protection winding if applicable. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary circuit at one point only. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 0.72/3kV, meaning 0.72kV system voltage and 3kV power-frequency withstand voltage.
Q: Can this CT be used for outdoor applications?
A: No, it is designed for indoor use only, typically in CGIS switchgear.
Q: What accuracy classes are available?
A: The CT offers multiple accuracy combinations, including metering classes (e.g., 0.2S, 0.5S) and protection classes (e.g., 5P, 10P).
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) 2COSφ=0.5 (0.2/0.5S) | Accuracy class & rated output (VA) 2COSφ=0.5 (0.5) | Accuracy class & rated output (VA) 2COSφ=0.5 (5P10) | Accuracy class & rated output (VA) 2COSφ=0.5 (5P15) | Short-time thermal current Ith (kA/S) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|
| 20-150 | 0.2(5)/0.5(5) | 10 | 15 | 15 | 10 | 100 I1n | 250 I1n | 30 |
| 200 | 0.2(5)/5P 0.5(5)/5P | 10 | 15 | 15 | 10 | 25 | 63 | 30 |
| 300 | 0.2(5)/5P 0.5(5)/5P | 10 | 15 | 15 | 10 | 31.5 | 80 | 30 |
| 400-600 | 0.2(5)/5P 0.5(5)/5P | 10 | 15 | 15 | 10 | 31.5/2 | 80 | 30 |
| 800-1600 | 0.2(5)/5P 0.5(5)/5P | 10 | 15 | 15 | 10 | 31.5/4 | 80 | 30 |
| 2000-2500 | — | 10 | 15 | 15 | 10 | 31.5/4 | 80 | 30 |
Dimension & outline drawing of LZZBJ18-35G3-175-CGIS — click image to zoom / view original.
This is an indoor single-phase epoxy resin cast current transformer for 35kV systems, used to step primary current down to a 5A or 1A secondary for metering and protection. The dry epoxy casting is the defining feature: it removes the liquid-insulation maintenance burden of oil-filled units and gives a compact, sealed body suited to switchgear and CGIS enclosures.
The LZZBJ18-35G3-175-CGIS carries an insulation level of 40.5/95/185kV at 50Hz or 60Hz. Accuracy combinations include 0.2(5)/0.5(5) and 0.2(5)/5P, with rated outputs of 10VA and 15VA at 2COSφ=0.5. Short-time thermal current reaches 31.5kA/4s with 80kA dynamic rating on the larger ratios; weight is 30kg. Compliance follows the GB/T 20840 series, with test certificates and drawings available [On Request].
Typical deployment is indoor switchgear in infrastructure such as rail, data centres, hospitals and water works. Earth the secondary at one point and never open-circuit it while energized. Specify only the accuracy class the application needs, since overspecification wastes budget. Ratio and accuracy combinations are customizable; consult the nameplate and datasheet for exact ratings.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.