Indoor single-phase epoxy resin casting current transformer complying with GB/T20840.1/2 and IEC61869-1/2 standards, insulation level 12/42/75kV, rated frequency 50/60Hz, secondary rated current 5A or 1A. Optional primary current ranges:20-150A、200A、300A、400A、500A、600-800A、1000-1250A; accuracy combinations:0.2S/510P10、0.5S/510P10、0.2S/0.5S, corresponding rated output:10VA for 0.2S,10VA for 0.5S,15VA for 510P10; short-time thermal current 16–64 kAS, rated dynamic stable current 40–160 kA, net weight 16kg, ambient operating temperature -5℃~+40℃.
Indoor 10kV cast-resin current transformer for MV switchgear, offering high accuracy and thermal stability.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ60-10 | Factory nameplate marking |
| Primary Voltage | 10kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary in series with the line. Secondary terminals: 1S1-1S2 for metering, 2S1-2S2 for protection. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What is the insulation level of this CT?
A: The insulation level is 12/42/75kV, meaning 12kV system voltage, 42kV power-frequency withstand, 75kV lightning impulse withstand.
Q: Can this CT be used for both metering and protection?
A: Yes, it offers accuracy combinations like 0.2S/5P10, with separate secondary windings for metering and protection.
Q: What is the weight of this CT?
A: The net weight is 16kg.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Rated output (VA) COSφ=0.8 (0.2/0.5/5P) | Rated output (VA) COSφ=0.8 (10P) | Short-time thermal current Ith (kA/S) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|---|
| 20-150 | 0.2(5)/5(10)P10 0.5(5)/5(10)P10 0.2(5)/0.5(5) | 10 | 10 | 100/1n | 250/1n | 16 |
| 200 | 0.2(5)/5(10)P10 0.5(5)/5(10)P10 0.2(5)/0.5(5) | 10 | 10 | 16 | 40 | 16 |
| 300 | 0.2(5)/5(10)P10 0.5(5)/5(10)P10 0.2(5)/0.5(5) | 10 | 10 | 24 | 60 | 16 |
| 400 | 0.2(5)/5(10)P10 0.5(5)/5(10)P10 0.2(5)/0.5(5) | 10 | 10 | 30 | 75 | 16 |
| 500 | 0.2(5)/5(10)P10 0.5(5)/5(10)P10 0.2(5)/0.5(5) | 10 | 10 | 40 | 100 | 16 |
| 600-800 | 0.2(5)/5(10)P10 0.5(5)/5(10)P10 0.2(5)/0.5(5) | 10 | 10 | 48 | 120 | 16 |
| 1000-1250 | 0.2(5)/5(10)P10 0.5(5)/5(10)P10 0.2(5)/0.5(5) | 10 | 10 | 64 | 160 | 16 |
Dimension & outline drawing of LZZBJ60-10 — click image to zoom / view original.
The LZZBJ60-10 is a 10 kV indoor single-phase current transformer designed for metering and protection duties in medium-voltage switchgear, and it is engineered against the IEC 61869, GB/T 20840 and IEEE C57.13 standard families. Its dry epoxy resin cast body and pillar-type format keep the footprint compact, which helps when cabinet space and switchroom layout are tight.
Accuracy classes of 0.2(S), 0.5(S) and 5(10)P10 are available with a rated burden of 10 VA, and the 20-150 A range carries short-time thermal current of 100/1n kA/S and dynamic stability of 250/1n kA. Insulation is rated 12/42/75kV at 50/60Hz, and the unit weighs 16kg. Unlike fuse-protected designs, this CT has no integral primary fuse, so protection coordination must be handled by the upstream scheme.
Deployment is indoor, in substation bays and busbar metering and protection circuits, within an ambient range of -5℃~+40℃. Earth the secondary at one point and equalise potential before energising; never open-circuit a secondary while the primary is live. DC or non-standard frequencies are not applicable. OEM branding and a routine test document package are available, with ratio and class options quoted on request.
Same product family, different ratings — compare before you specify.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1911 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1775 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.
Current Transformer Applied to CGIS Gas Insulated Switchgear
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.