LZZBJ9-12/185h/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-12-185h-2s-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation.
12 kV epoxy-cast CT with a configurable accuracy menu (0.2 and 0.5 metering plus 5P10/5P15/5P20 protection), 20–3150 A, 10–20 VA.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ9-12-185h-2s-4s | Factory nameplate marking |
| Primary Voltage | 12kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What does the h in LZZBJ9-12/185h mean?
A: It marks the taller cast body of this frame, which is what allows the wider winding and accuracy combinations.
Q: Can metering and protection classes be chosen independently?
A: Yes. The datasheet lists six pairings from 0.2/5(5P10) to 0.2/0.5/5(5P20), so the protection factor can be selected separately from the metering class.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current I1n (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 | Short-time thermal current Ith (kA/s) | Rated dynamic current Idyn (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 20-150 | 0.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20) | 10 15 | 15 | 200/1n | 500/1n |
| 200-300 | 0.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20) | 10 15 | 15 | 45/1n | 100/1n |
| 400 | 0.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20) | 10 15 | 15 | 55/1n | 130/1n |
| 500-600 | 0.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20) | 10 15 | 15 | 63/1n | 130/1n |
| 800-1250 | 0.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20) | 15 20 | 15 | 80/1n | 160/1n |
| 1500-3150 | 0.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20) | 15 20 | 15 | 100/1n | 160/1n |
Dimension & outline drawing of LZZBJ9-12-185h-2s-4s — click image to zoom / view original.
LZZBJ9-12/185h/2s(4s) is the 12 kV model with the widest accuracy menu in the series. The h suffix marks a taller cast body than the 175b frame, and the unit is offered with two or four cores covering 20 A to 3150 A primary.
Rather than a single accuracy string, the datasheet lists combinations: 0.2/5(5P10), 0.2/5(5P15), 0.2/5(5P20), 0.2/0.5/5(5P10), 0.2/0.5/5(5P15) and 0.2/0.5/5(5P20). Rated output is 10 VA and 15 VA in the lower bands and 15 VA and 20 VA from 800 A upward. This lets a specifying engineer pick the protection factor independently of the metering class instead of accepting a fixed pairing.
The practical use is a feeder family where metering accuracy and protection speed are both tight: the 0.2 core handles billing, the 5P20 core handles short-circuit clearing, and the two are isolated in one casting. Specify the exact combination from the table, because the same model code can be delivered with several different core pairings.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Cast Current Transformer 12kV
Indoor single-phase epoxy resin casting CT, compliant with GB/T20840.1/2 & IEC61869-1/2, insulation level 12/42/75kV, 50/60Hz, secondary current 5A/1A. Optional primary current ranges:20-200A、300A、400A、500-600A、800-1000A、1200-3150A; multiple accuracy combinations of metering and protection grades, matched thermal/dynamic withstand parameters for each range, net weight 62kg, operating temperature -5℃~+40℃.
Indoor Single-phase Epoxy Cast Current Transformer 12kV
LZZBJ9-12/198b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-198b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, accuracy class 0.5/1.0/3.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.
Indoor Single-phase Epoxy Cast Current Transformer 12kV
LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-225b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.