KEMA & ISO 9001/14001 Certified|Exporting to 50+ Countries (IEC 61869-3 / IEEE C57.13)
24/7 Global Engineering Hotline: 86 18852046268|sales@potentialtransformers.com
中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTLZZBJ9-12-185h-2s-4s
LZZBJ9-12/185h/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer
12kVLZZBJ9-12-185h-2s-4s
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 12kV
Secondary Metering (1S1 - 1S2):5A/1A ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:LZZBJ9-12-185h-2s-4s

LZZBJ9-12/185h/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer

LZZBJ9-12/185h/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-12-185h-2s-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation.

Key Engineering Advantages

  • 12kV indoor epoxy cast CT with multiple structures and dual-ratio secondary tapping
  • excellent thermal and dynamic stability
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: LZZBJ9-12-185h-2s-4s

Electrical Parameters

Primary Rated Voltage (Un):12kV
Secondary Winding Currents:5A/1A
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Insulation Level (BIL):12/42/75kV
Environmental Class:Ambient: -5℃~+40℃
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

12 kV epoxy-cast CT with a configurable accuracy menu (0.2 and 0.5 metering plus 5P10/5P15/5P20 protection), 20–3150 A, 10–20 VA.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeLZZBJ9-12-185h-2s-4sFactory nameplate marking
Primary Voltage12kVRated voltage test (IEC 61869-1/3)
Secondary Current5A/1ARatio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)12/42/75kVPower-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
EnvironmentAmbient: -5℃~+40℃Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor MV switchgear panels (10kV class)
  • Metering and protection applications
  • Dual-ratio applications with secondary tapping
  • Environments -5°C to +40°C

Not Recommended For

  • Outdoor installations
  • Gas-insulated switchgear (GIS)
  • High-voltage transmission systems (>12kV)
  • DC systems

Topology & Wiring

secondary terminals 1S1/1S2 (protection winding 2S1-2S2). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What does the h in LZZBJ9-12/185h mean?

A: It marks the taller cast body of this frame, which is what allows the wider winding and accuracy combinations.

Q: Can metering and protection classes be chosen independently?

A: Yes. The datasheet lists six pairings from 0.2/5(5P10) to 0.2/0.5/5(5P20), so the protection factor can be selected separately from the metering class.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

LZZBJ9-12-185h-2s-4s
6 cols · 6 rows

LZZBJ9-12/185h/2s (4s) Series Current Transformer — Technical Data

Rated primary current I1n (A)Accuracy classCombinedAccuracy class & rated output (VA) COSφ=0.8Short-time thermal current Ith (kA/s)Rated dynamic current Idyn (kA)Weight (kg)
20-1500.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20)10 1515200/1n500/1n
200-3000.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20)10 151545/1n100/1n
4000.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20)10 151555/1n130/1n
500-6000.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20)10 151563/1n130/1n
800-12500.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20)15 201580/1n160/1n
1500-31500.2/5(5P10) 0.2/5(5P15) 0.2/5(5P20) 0.2/0.5/5(5P10) 0.2/0.5/5(5P15) 0.2/0.5/5(5P20)15 2015100/1n160/1n
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of LZZBJ9-12-185h-2s-4s — click image to zoom / view original.

Product Overview

About This Product

LZZBJ9-12-185h-2s-4s

LZZBJ9-12/185h/2s(4s) is the 12 kV model with the widest accuracy menu in the series. The h suffix marks a taller cast body than the 175b frame, and the unit is offered with two or four cores covering 20 A to 3150 A primary.

Rather than a single accuracy string, the datasheet lists combinations: 0.2/5(5P10), 0.2/5(5P15), 0.2/5(5P20), 0.2/0.5/5(5P10), 0.2/0.5/5(5P15) and 0.2/0.5/5(5P20). Rated output is 10 VA and 15 VA in the lower bands and 15 VA and 20 VA from 800 A upward. This lets a specifying engineer pick the protection factor independently of the metering class instead of accepting a fixed pairing.

The practical use is a feeder family where metering accuracy and protection speed are both tight: the 0.2 core handles billing, the 5P20 core handles short-circuit clearing, and the two are isolated in one casting. Specify the exact combination from the table, because the same model code can be delivered with several different core pairings.

Other Models in This Series

Same product family, different ratings — compare before you specify.

LZZBJ9-12/195b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV
0.5kV
Current Transformer50/60Hz

LZZBJ9-12-195b-4s

Indoor Single-phase Epoxy Cast Current Transformer 12kV

Indoor single-phase epoxy resin casting CT, compliant with GB/T20840.1/2 & IEC61869-1/2, insulation level 12/42/75kV, 50/60Hz, secondary current 5A/1A. Optional primary current ranges:20-200A、300A、400A、500-600A、800-1000A、1200-3150A; multiple accuracy combinations of metering and protection grades, matched thermal/dynamic withstand parameters for each range, net weight 62kg, operating temperature -5℃~+40℃.

Accuracy Class0.5/1.0/3.0
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs
LZZBJ9-12/198b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV
12kV
Current Transformer50/60Hz

LZZBJ9-12-198b-4s

Indoor Single-phase Epoxy Cast Current Transformer 12kV

LZZBJ9-12/198b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-198b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, accuracy class 0.5/1.0/3.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Accuracy Class0.5/1.0/3.0
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs
LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV
12kV
Current Transformer50/60Hz

LZZBJ9-12-225b-4s

Indoor Single-phase Epoxy Cast Current Transformer 12kV

LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-225b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.

Accuracy Class0.2/0.5/1.0
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
ComplianceIEC 61869 / GB/T 20840
View Specs