Indoor single-phase epoxy resin casting CT, compliant with GB/T20840.1/2 & IEC61869-1/2, insulation level 12/42/75kV, 50/60Hz, secondary current 5A/1A. Optional primary current ranges:20-200A、300A、400A、500-600A、800-1000A、1200-3150A; multiple accuracy combinations of metering and protection grades, matched thermal/dynamic withstand parameters for each range, net weight 62kg, operating temperature -5℃~+40℃.
12 kV four-core epoxy-cast CT, 200–3150 A, 0.2(5)/0.2(5)/5P/5P at 20–40 VA, 82 kg.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | IEC 61869 / GB/T 20840 |
| Model Code | LZZBJ9-12-195b-4s | Factory nameplate marking |
| Primary Voltage | 0.5kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | [On Request] | Ratio check at rated frequency |
| Accuracy Class | 0.5/1.0/3.0 | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | [On Request] | Power-frequency & lightning impulse withstand |
| Standards | IEC 61869 / GB/T 20840 | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | [On Request] | Per datasheet limits |
Ideal For
Not Recommended For
Connect primary through the bushing. Secondary terminals: 1S1 and 1S2 for metering, 2S1 and 2S2 for protection. Never open-circuit the secondary while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869-2 terminal markings.
Compliant with: IEC 61869 / GB/T 20840
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: Why does the 195b weigh 82 kg?
A: The 200–3150 A window and the four-core winding package require a substantially larger casting than the 26 kg 175b frame.
Q: Is the 195b electrically different from the 198b and 225b?
A: No. The three share one datasheet and differ in cast body dimensions; they are published together as variants of the same design.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) COSφ=0.8 | Short-time thermal current (kA/S) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 200-200 | 0.2(5) 0.2(5) 5P/5P 5P/5P | 20 20 25 20 15 | 150 15 | 150 375 | 82 |
| 300 | 0.2(5) 0.2(5) 5P/5P 5P/5P | 20 20 25 20 15 | 31.5 45 | 80 112.5 | 82 |
| 400 | 0.2(5) 0.2(5) 5P/5P 5P/5P | 20 20 25 20 15 | 45 63 | 112.5 130 | 82 |
| 500-600 | 0.2(5) 0.2(5) 5P/5P 5P/5P | 20 20 25 20 15 | 63 80 | 130 160 | 82 |
| 800-1000 | 0.2(5) 0.2(5) 5P/5P 5P/5P | 30 30 40 30 20 | 80 100 | 160 200 | 82 |
| 1200-3150 | 0.2(5) 0.2(5) 5P/5P 5P/5P | 30 30 40 30 20 | 100 | 160 | 82 |
Dimension & outline drawing of LZZBJ9-12-195b-4s — click image to zoom / view original.
LZZBJ9-12/195b/4s is the 12 kV four-core model built for the 200–3150 A band, where the primary bar is large and the secondary wiring is dense. The cast body weighs 82 kg, roughly three times the 26 kg of the 175b frame, because the larger window and the four-core winding package need more epoxy and more iron.
Its datasheet lists 20/20/25/20/15 VA across the cores, with accuracy combinations of 0.2(5), 0.2(5), 5P and 5P. From 800 A upward the outputs rise to 30/30/40/30/20 VA, and short-time thermal current reaches 100 kA with a 160 kA dynamic rating at 1200–3150 A. The four cores are typically split two for metering and two for protection.
This model shares its electrical datasheet with LZZBJ9-12/198b/4s and LZZBJ9-12/225b/4s; the three are published together as dimensional variants of one design. Order by the frame that fits the panel, and confirm which of the three bodies the drawing specifies before releasing the purchase order.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Cast Current Transformer 12kV
LZZBJ9-12/198b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-198b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, accuracy class 0.5/1.0/3.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.
Indoor Single-phase Epoxy Cast Current Transformer 12kV
LZZBJ9-12/225b/4s Indoor Single-phase Epoxy Cast Current Transformer 12kV (LZZBJ9-12-225b-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A, accuracy class 0.2/0.5/1.0. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to IEC 61869 / GB/T 20840.
Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV
LZZBJ9-12GY2 Indoor Single-phase Epoxy Resin Casting Current Transformer,12kV is designed for metering and protection in power systems. Key ratings: primary voltage 12kV. Design: Dry Epoxy Resin, 50/60Hz operation. Conforms to GB/T 17201.