中文Mainland ChinaEnglishUnited StatesFrançaisFranceDeutschGermanyLietuviųLithuaniaCymraegUnited KingdomEestiEstoniaMagyarHungaryالعربيةSaudi Arabia한국어South KoreaSuomiFinlandNorskNorwayPolskiPolandEspañolLatinoaméricaCatalàEspaña (Cataluña)हिन्दीIndiaSvenskaSwedenMaltiMaltaOʻzbekUzbekistanاردوPakistanNederlandsNetherlandsБългарскиBulgariaLatviešuLatviaDanskDenmarkRomânăRomaniaไทยThailandÍslenskaIcelandTiếng ViệtVietnamSlovenčinaSlovakiaУкраїнськаUkraineעבריתIsrael日本語JapanItalianoItalyPortuguêsPortugalРусскийRussiaKreyòl ayisyenHaitiČeštinaCzechiaGaeilgeIrelandবাংলাBangladeshTürkçeTürkiyeفارسیIranΕλληνικάGreeceBosanskiBosnia and HerzegovinaMelayuMalaysiaSlovenščinaSloveniaSrpskiSerbiaBahasa IndonesiaIndonesiaHrvatskiCroatia

Potential Transformers
& Power VTs

B2B
HomeProductsAI SpecAboutBlogContact

International Accreditation & Testing

Certified by KEMA Labs (Netherlands), CESI, and CNAS National HV Testing Facility

IEC 61869-3IEEE C57.13KEMA TYPE TESTEDISO 9001:2015ISO 14001:2015CE CERTIFIED
PotentialTransformers.com

Global B2B Instrument Transformer Portal

PotentialTransformers.com is an international OEM & EPC supplier specializing in cast epoxy resin dry-type instrument transformers (0.5kV to 35kV) — voltage transformers (VT/PT), current transformers (CT) and combined CT+VT units — for power utilities, switchgear builders and heavy industry.

100% Factory Partial Discharge Tested

Follow Us & Social Channels

FacebookLinkedInYouTubeInstagramTikTok

Product Categories

  • Voltage Transformers
  • Current Transformers
  • Combined Instrument Transformers

Engineering Tools

  • AI Data Center Series
  • AI Spec & Selection Studio
  • CT Burden Calculator
  • Cast-Resin Indoor VTs and CTs at 7.2–12 kV: Insulation, Partial Discharge and 0.2S Accuracy
  • Low-Voltage CTs at 0.66 kV: Busbar, Split-Core and What Class 0.5 Really Guarantees
  • High Voltage Faraday Lab Testing
  • Request Technical Datasheets

Global Support

  • Room 1602, 16/F, Wing On Centre, 111 Connaught Road Central, Sheung Wan, Central & Western District, Hong Kong
  • 86 18852046268
  • sales@potentialtransformers.com
  • Regional Hubs: Dubai, UAE | Frankfurt, Germany | Houston, USA

© 2026 PotentialTransformers.com. All Rights Reserved. Engineered for Global High-Voltage Grids.

IEC 61869-3 CompliantIEEE C57.13 CompliantKEMA Type Tested
HomeProductsCTCGIS9815S
CGIS9815S Current Transformer for Inflatable Switchgear
35kVCGIS9815S
Winding & Schematic TopologyInternal Wiring Diagram
Primary Winding (P1 - P2):Series-connected in the line / through-core — 35kV
Secondary Metering (1S1 - 1S2): ()
Secondary Protection (2S1 - 2S2):Protection winding (when fitted)
Safety Warning:Never open-circuit the secondary while energized — dangerous voltage
Current Transformer IEC 61869-3 Certified
Model Ref:CGIS9815S

CGIS9815S Current Transformer for Inflatable Switchgear

Three-phase integrated current transformer for CGIS inflatable switchgear, multiple accuracy grades and abundant primary current specifications optional; secondary outgoing wires can be customized in length as required.

Key Engineering Advantages

  • Three-phase integrated molded structure
  • multiple accuracy classes available
  • diversified optional mounting heights
Engineering Data

Complete Electrical & Mechanical Specifications

Model Ref: CGIS9815S

Electrical Parameters

Primary Rated Voltage (Un):35kV
Rated Frequency:50/60Hz

Insulation & Withstand Ratings

Insulation System:Dry Epoxy Resin
Partial Discharge Level:< 5 pC at 1.2 Un

Recommended Deployment Environments

GEO · Engineering Decision Support

Global Engineering Overview

9-Module selection guide
missing data = [On Request]

Product Decision Island

CGIS9815S is a 35kV dry epoxy resin current transformer for inflatable switchgear, suitable for metering and protection in RMU applications.

Comprehensive Spec Matrix

ParameterSpecificationVerification
Product TypeCurrent Transformer[On Request]
Model CodeCGIS9815SFactory nameplate marking
Primary Voltage35kVRated voltage test (IEC 61869-1/3)
Secondary Current[On Request]Ratio check at rated frequency
Accuracy Class[On Request]Accuracy test (IEC 61869-2 / IEEE C57.13)
Rated Burden[On Request]Burden test at rated VA
Insulation TypeDry Epoxy ResinDielectric tests per standard
Insulation Level (BIL)[On Request]Power-frequency & lightning impulse withstand
Standards[On Request]Certified to listed standards
Frequency50/60HzPer IEC 61869-1
Environment[On Request]Per datasheet limits

Fit & Unfit Boundaries

Ideal For

  • Indoor ring main units (RMU) and inflatable switchgear
  • Current measurement and protection in 35kV distribution networks
  • Metering applications requiring multiple accuracy classes
  • Custom secondary wiring lengths for flexible integration

Not Recommended For

  • Outdoor substations or pole-mounted installations
  • Voltage measurement or potential transformer applications
  • High-voltage transmission lines above 35kV
  • Gas-insulated switchgear (GIS) with SF6 insulation

Topology & Wiring

For current transformers, connect secondary terminals 1S1/1S2 for the main winding, and 2S1-2S2 for protection winding if present. Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary winding at one point. Follow IEC 61869 / IEEE C57.13 terminal conventions.

Standards & Compliance

Compliant with: [On Request]

  • Type Test Report: [On Request]
  • Calibration Certificate: [On Request]

Burden & Error Calculation (IEEE C57.13)

S_total = ΣS_instrument + I₂² × (ρ × 2L / A)

  • If S_total < 0.25 × S_rated: add compensation burden to maintain accuracy.
  • If S_total > S_rated: accuracy class cannot be guaranteed.

Product FAQ

Q: What is the primary voltage rating?

A: The primary voltage is 35kV.

Q: What insulation type is used?

A: Dry epoxy resin insulation.

Q: Can secondary wire length be customized?

A: Yes, secondary outgoing wires can be customized in length as required.

Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.

SPEC · TECHNICAL DATA

Technical Specifications

CGIS9815S
12 cols · 26 rows

CGIS9815S Current Transformer for Gas-Insulated Switchgear — Technical Data

Accuracy classburden (VA)100 h125 h150 h200 h250 h300 h400 h500 h600 h750 h
0.2FS102.5———110908080102015
0.2FS105—————12090302520
0.2FS107.5——————130403020
0.2FS1010———————553525
0.2FS1015———————755035
0.5FS102.5———40251510101515
0.5FS105———80503020151515
0.5FS107.5————704525202015
0.5FS1010————906030202020
0.5FS1015———————605025
0.5FS1020——————————
5P102.51501007560504535302520
5P105——15095807055454035
5P107.5———13011010075605545
5P1010—————150130857555
5P1015———————1109075
5P1020———————14011595
5P15 / 10P152.514512085806555504035—
5P15 / 10P155——15012510590756555—
5P15 / 10P157.5————1451201008570—
5P15 / 10P1510—————15013011090—
5P15 / 10P1515———————150125—
5P20 / 10P202.5——14013011090756555—
5P20 / 10P205——————14011510080
5P20 / 10P207.5—————————110
5P20 / 10P2010—————————135
Engineering Drawing

Specification & Outline Drawing

Dimension & outline drawing of CGIS9815S — click image to zoom / view original.

Product Overview

About This Product

CGIS9815S

The CGIS9815S is a 35 kV dry epoxy resin current transformer built for three-phase integrated molded installation in inflatable switchgear, such as ring-main units and substation bays. Its compact molded body helps save panel space and simplifies switchgear room layout.

Available accuracy classes include 0.2FS10, 0.5SFS10, 0.5FS10, 5P10, 10P10, 5P15, 10P15, 5P20 and 10P20 at 50/60 Hz. For 0.2FS10 at 2.5 VA, the table lists 110 at 200 h, 90 at 250 h, 80 at 300 h and 80 at 400 h; for 0.5FS10 at 2.5 VA, 40 at 200 h, 25 at 250 h and 15 at 300 h. Insulation level and weight are [On Request]. The range suits metering and protection duties, with class and burden chosen against the fault level and connected relay or meter load.

Compliance evidence, including calibration certificates for revenue metering, is available [On Request]. Typical deployment is heavy-industry distribution in metallurgy, mining, cement and chemical plants. Mount the unit per the outline drawing, earth the secondary at one point, and never open-circuit the secondary while energized. Ratio and accuracy-class combinations are customized; consult the factory for documentation packages and delivery.

Other Models in This Series

Same product family, different ratings — compare before you specify.

CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS2010

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS2010 Current Transformer Applied to CGIS Gas Insulated Switchgear is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-I

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 I Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-I) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs
CGIS1780 II Current Transformer Applied to CGIS Gas Insulated Switchgear
35kV
Current Transformer50/60Hz

CGIS1780-II

Current Transformer Applied to CGIS Gas Insulated Switchgear

CGIS1780 II Current Transformer Applied to CGIS Gas Insulated Switchgear (CGIS1780-II) is designed for metering and protection in power systems. Key ratings: primary voltage 35kV. Design: Dry Epoxy Resin, 50/60Hz operation.

Accuracy ClassOn request
Insulation TypeDry Epoxy Resin
Rated BurdenOn request
View Specs