LZZBJ9-12/150b/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-12-150b-2s-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation.
12 kV general-purpose epoxy-cast CT, 20–1250 A, 2 or 4 cores, 0.2(5)/0.5(5) at low ratios and 5P10–5P20 at high ratios.
| Parameter | Specification | Verification |
|---|---|---|
| Product Type | Current Transformer | [On Request] |
| Model Code | LZZBJ9-12-150b-2s-4s | Factory nameplate marking |
| Primary Voltage | 12kV | Rated voltage test (IEC 61869-1/3) |
| Secondary Current | 5A/1A | Ratio check at rated frequency |
| Accuracy Class | [On Request] | Accuracy test (IEC 61869-2 / IEEE C57.13) |
| Rated Burden | [On Request] | Burden test at rated VA |
| Insulation Type | Dry Epoxy Resin | Dielectric tests per standard |
| Insulation Level (BIL) | 12/42/75kV | Power-frequency & lightning impulse withstand |
| Standards | [On Request] | Certified to listed standards |
| Frequency | 50/60Hz | Per IEC 61869-1 |
| Environment | Ambient: -5℃~+40℃ | Per datasheet limits |
Ideal For
Not Recommended For
connect primary through bushing; secondary terminals 1S1/1S2 for metering, 2S1/2S2 for protection (if dual-ratio). Never open-circuit the secondary of a CT while energized - hazardous voltage. Ground the secondary circuit at one point only. Follow IEC 61869-2 terminal markings.
Compliant with: [On Request]
S_total = ΣS_instrument + I₂² × (ρ × 2L / A)
Q: What does 2s(4s) mean in the model code?
A: It denotes that the transformer is available with two or four secondary cores; the electrical design is otherwise the same.
Q: Which accuracy class applies above 300 A?
A: The protection core is offered as 5P10, 5P15 or 5P20 depending on the ratio, with 10 VA on the metering cores.
Missing fields are marked [On Request] — never fabricated. M2/M5/M6 verification rows follow IEC 61869 / IEEE C57.13 conventions.
| Rated primary current (A) | Accuracy classCombined | Accuracy class & rated output (VA) | Short-time thermal current (kA/s) | Rated dynamic current (kA) | Weight (kg) |
|---|---|---|---|---|---|
| 20-200 | 0.2(5)/0.5(5) | 10 10 15 15 | 150/1 | 375/1 | — |
| 300-400 | 0.2(5)/5P10 | 10 10 15 15 | 31.5 | 80 | — |
| 500 | 0.2(5)/5P15 | 10 10 15 15 | 31.5 | 80 | — |
| 600-800 | 0.2(5)/5P15 | 10 10 15 15 | 80 | 160 | — |
| 1000-1250 | 0.2(5)/5P20 | 10 10 15 15 | 100 | 160 | — |
Dimension & outline drawing of LZZBJ9-12-150b-2s-4s — click image to zoom / view original.
LZZBJ9-12/150b/2s(4s) is a 12 kV indoor epoxy-cast current transformer offered with either two or four secondary cores from the same cast body. It is the general-purpose 12 kV unit in the range: 20 A to 1250 A primary, 5 A or 1 A secondary, for metering and protection in medium-voltage switchgear.
Accuracy depends on the ratio band. From 20 A to 200 A the unit is specified as 0.2(5)/0.5(5) with 10 VA, 10 VA, 15 VA and 15 VA across its cores, and short-time thermal current of 150 times primary for 1 s. From 300 A upward the protection core moves to 5P10, 5P15 or 5P20 and the thermal rating is stated in absolute terms, 31.5 kA at 300–500 A rising to 100 kA at 1000–1250 A.
Because the same frame covers both the 0.2(5) small-ratio band and the 5P20 high-ratio band, the model is often used where a panel family needs one footprint across feeders of different rating. Specify the core count (2s or 4s) explicitly: the electrical data is shared, but the terminal arrangement and wiring space differ.
Same product family, different ratings — compare before you specify.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-12/175b/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-12-175b-2s-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Resin Casting Current Transformer
LZZBJ9-12/185h/2s(4s) Indoor Single-phase Epoxy Resin Casting Current Transformer (LZZBJ9-12-185h-2s-4s) is designed for metering and protection in power systems. Key ratings: primary voltage 12kV, secondary voltage 5A/1A. Design: insulation level 12/42/75kV, Dry Epoxy Resin, 50/60Hz operation.
Indoor Single-phase Epoxy Cast Current Transformer 12kV
Indoor single-phase epoxy resin casting CT, compliant with GB/T20840.1/2 & IEC61869-1/2, insulation level 12/42/75kV, 50/60Hz, secondary current 5A/1A. Optional primary current ranges:20-200A、300A、400A、500-600A、800-1000A、1200-3150A; multiple accuracy combinations of metering and protection grades, matched thermal/dynamic withstand parameters for each range, net weight 62kg, operating temperature -5℃~+40℃.